CLEARANCES TO COMBUSTIBLES

It is of utmost importance that the clearances to combustible materials be strictly adhered to during

installation of the stove. Refer to the tables below :

• Floor to ceiling height must be at least 7’ (2.13m) in all cases.
• Do not place any combustible material within 4’ (1.2m) of the front of the unit.
• The clearance between the flue pipe and a wall are valid only for vertical walls and for vertical flue

pipe.

• The chimney connector must not pass through an attic or roof space, closet or similar concealed

space, a floor, or a ceiling.

• For Canadian installations, where passage through a wall, or partition of combustible construction

is desired, the installation must conform to CAN/CSA-B365.

• A flue pipe crossing a combustible wall must have a minimum clearance of 18” (457.2mm).
• To reduce flue clearances from combustible materials, contact your local safety department.

Single Wall Pipe

Model A

B

C

D

E

F

3000

14

(358mm)

20

(508mm)

17.5

(445mm)

30.5

(775mm)

11

(279mm)

24

(610mm)