United States Stove Company 3000 (L) Manuel d'utilisation

Page 8

Advertising
background image

8

Ussc

FLOOR PROTECTOR

Your wood stove should be placed on a 1 inch, non-combustible surface with a k factor of 0.84. For

multiple layers, add R-values of each layer to determine the overall R-value. The R value for the

required board is 1.2. If there is a horizontal section of chimney connector, the floor protector should

go under it and 2 inches beyond each side

Convert specification to R-value:

k-factor is given with a required thickness (T) in inches: R=1/k x T

C-factor is given: R=1/C

Example:

If the floor protector is 4” brick with a C-factor of 1.25 over 1/8” mineral board with a “k”

factor

of 0.29 the total R-value of the system is:

4” brick C=1.25, R=1/1.25=0.8

1/8” mineral board K=0.29, R=1/0.29 x 0.125=0.431

Total R = Rbrick + Rmineral = 0.8 + 0.431 = 1.231

Total R is greater than 1.2, the system is acceptable.

The floor protector should exceed the stove as follows:

- Canadian installations require 8” (203mm)

Model

Front

Sides

Rear

3000

26”

(660mm)

8”

(203mm)

6”

(152mm)