operating Instructions and owner’s Manual

enerco | Compact Unit Heater

5

SIDE VIEw

Date: _______________________________________

State/Province: _______________________________
State/Province: _______________________________
Service Technician: ____________________________

SHIppINg

The heater is completely assembled. Installation instructions,
two mounting brackets (shipped loose), and a flue transition are
included. Check the unit for shipping damage. The receiving party
should contact the last carrier immediately if any shipping damage
is found.

REQUIREMENTS – CSA IN THE USA

Installation of gas unit heaters must conform with local building
codes or, in the absence of local codes, with the current National
Fuel Gas Code ANSI Z223.1.

Installation in aircraft hangers must be in accordance with the
current Standard for Aircraft Hangers ANSI/NFPA No. 409.

Installation in parking structures must be in accordance with the
current Standard for Parking Structures ANSI/NFPA No. 88A.

Installation in repair garages must be in accordance with the
current Standard for Repair Garages ANSI/NFPA No. 88B.

These units are approved for residential applications. For
installation in a residential garage these units must be installed
so that burners and ignition source are located no less than 18”
(457mm) above floor. Heater must be located or protected to
avoid physical damage by vehicles. Refer to the National Fuel Gas
Code, ANSI Z223.1, current edition.

Authorities having jurisdiction should be consulted before NFPA
installation. Air for combustion and ventilation must conform
to the methods outlined in ANSI Z223.1, section 5.3, Air for
Combustion and Ventilation, or applicable provisions of local
building codes. The National Fuel Gas Code is available from:

American National Standard Institute Inc.
11 West 42nd Street
New York, NY 10036

These units are CSA International design certified. These unit
heaters are certified for installation to combustible material
as listed in table 1 and on unit rating plate. Accessibility and
service clearances must be observed in addition to fire protection
clearances.

All electrical wiring and ground for unit must be in accordance
with the regulations of the current National electric Code ANSI/
No. 70.

The National electric Code is available from:

National Fire Protection Association

1 Batterymarch Park

Po Box 9101

Quincy, MA 02269-9101

REQUIREMENTS – CSA IN CANADA

The instructions are intended only as a general guide and do not
supersede local codes in any way. Authorities having jurisdiction
should be consulted before installation. The installation must
conform with local building codes or in the absence of local
codes, with the current CSA B149.1, Natural Gas and Propane
Installation Code. All electrical wiring and grounding for the unit
must also comply with the Canadian Electrical Code CSA C22.1,
current edition.

These unit heaters are CSA International certified for the
clearances to combustible material listed on the rating plate
and

table 1. Adequate clearance around air openings into the

combustion chamber, clearances from combustible material, and
provisions for accessibility and for combustion and ventilation
air supply. Provision shall be made for service accessibility to the
heater. Note that fire protection clearances may be exceeded to
provide additional space for service and accessibility.

gARAgE INSTALLATIONS:

Installation in parking structures must be in accordance with the
current Standard for Parking Structures ANSI/NFPA No. 88A.

Installation in repair garages must be in accordance with the
current Standard for Repair Garages ANSI/NFPA No. 88B.

1. In a storage area, clearance from heaters to combustible

materials must be such that the material shall not attain a
temperature above 160°F by continuous operation of the unit.

2. Eight foot minimum clearance from the floor to the bottom

of the heater must be maintained. Refer to the CSA B149.1,
Natural Gas and Propane Installation Code

AIRCRAFT HANgER:

Installation of gas unit heaters must conform with local building
codes or, in the absence of local codes, with the current National
Fuel Gas Code ANSI Z223.1.

1. In an area where aircraft are housed or serviced, 10’

minimum clearance from highest surface of aircraft to bottom
of the heater must be maintained.

2. In other areas, 8’ minimum clearance from the floor to

bottom of heater must be maintained.

3. Heaters should be located so as to be protected from

damage from aircraft or other appliances needed for
servicing of aircraft. Refer to requirements of the enforcing
authorities.

TABLE 1

UNIT CLEARANCES


Top

Sides

Access Panel

Bottom

Rear

Single Wall Vent*

in

mm

in

mm

in

mm

1

25

1

25

18

457

in

mm

in

mm

in

mm

0

0

18

456

6

152

*except for listed clearance thimbles.