4.2 HORIZONTAL AIR TERMINAL INSTALLATION

4.3 EXTENDED HORIZONTAL AND CORNER AIR TERMINAL INSTALLATION

A.

Stretch the inner fl ex pipe to the required length

taking into account the additional length needed for

the

fi nished wall surface. Apply a heavy bead of the

high temperature sealant W573-0007 Mill Pac (not

supplied) to the inner sleeve of the air terminal. Slip

the vent pipe a minimum of 2” (50.8mm) over the inner
sleeve of the air terminal and secure with 3 #8 screws.

`
B.

Using the outer rigid pipe, slide over the outer combustion air
sleeve of the air terminal and secure with 3 #8 screws. Seal
using high temperature sealant W573-0002 (not supplied).

C.

Insert the vent pipes through the fi restop maintaining the required clearance to combustibles. Holding the air
terminal (lettering in an upright, readable position), secure to the exterior wall and make weather tight by sealing
with caulking (not supplied).

D.

From inside the house, using silicone, seal between the vent
pipe and the fi restop. Then slide the black trim collar over the
vent pipe up to the fi restop.

E.

If more vent pipe needs to be used to reach the appliance,
couple them together as illustrated. The vent system must
be supported approximately every 3 feet (0.9m) for both
vertical and horizontal runs. Use noncombustible strapping
to maintain the minimum clearance to combustibles.

The air terminal mounting plate may be recessed into the exterior wall or siding no greater than the depth of its
return fl ange.

23.7C

SCREWS

#10x2"

SEALANT

HIGH TEMP

2" (50.8mm) OVERLAP

CAULKING

7" (177.8mm) RIGID

PIPE

4" (101.6mm) FLEX PIPE

#8 X 1/2”SELF DRILLING

SCREWS & WASHERS

INNER COUPLER

OUTER COUPLER

HI-TEMP

SEALANT

OUTER

RIGID PIPE

INNER
FLEX PIPE

OUTER

RIGID PIPE

A 45° corner installation can have 0” (0mm) rise between the appliance
combustion air collar and the air terminal. In this case, vent lengths must be
kept to a maximum of 24” (609.6mm) . For longer vent lengths, a minimum
vertical rise of 24” (609.6mm) is required.

A. Follow the instructions for "HORIZONTAL AIR TERMINAL
INSTALLATION" section.

B. Continue adding components alternating inner and outer vent pipes. Ensure that
all inner vent pipes and elbows have sufficient vent spacers attached and each
component is securely fastened to the one prior. Attach the telescopic sleeve to the
vent run. Secure and seal. To facilitate completion, attach inner and outer couplers to
the air terminal.

C. Install the air terminal. See “HORIZONTAL AIR TERMINAL INSTALLATION” section. Extend the outer
telescopic sleeve; connect to the air terminal assembly. Fasten with self tapping screws and seal.

TELESCOPIC SLEEVE

VENTING

AIR TERMINAL

20" (508mm)
COUPLER

48.2A

TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE

RETURN FLANGE OF THE MOUNTING PLATE.

DO NOT ALLOW THE INNER FLEX PIPE TO BUNCH UP ON HORIZONTAL OR VERTICAL RUNS AND

ELBOWS. KEEP IT PULLED TIGHT.

!

WARNING

W415-0547 / J / 07.16.13

20

EN