Installation & Servicing Instructions Rinnai E-Series

76

Code

Description

Solution

No signal from the fan

The fan is not running. Check the wiring to the fan and the control unit and/
or the 24 volt power supply to the fan
Wiring and voltage are OK and error is repeated. Replace the fan

Negative pressure on vent
system (pressure difference)

Check vent system. Vent system and air intake system must be installed
according installation instructions.
IF vent system is OK:
Replace fan

internal shut down of supply
sensor T1

Check the data in Error mode. Boiler data during error:
1 Error

= 31

2 Operational status = 00
3 Flow temp.

= 230

4 Return temp.

= xx*

5 kW burner

= 00**

6 % pomp

= xx*

* = variable values
**= x3415=BTU/hr
Check the wiring. check the wiring for the sensor

The wiring is OK but the error is repeated. Remove the plug from the fl ow
sensor as a result of which Error 36 occurs
Replace the sensor.

Shut down of return sensor T2

Check the data in Error mode. Boiler data during error:
1 Error

= 32

2 Operational status = 00
3 Flow temp.

= xx*

4 Return temp.

= 230

5 kW burner

= 00**

6 % pomp

= xx*

* = variable values
**= x3415=BTU/hr
Check the wiring. check the wiring for the sensor

The wiring is OK but the error is repeated. Remove the plug from the fl ow
sensor as a result of which Error 37 occurs
Replace the sensor.

contact for supply sensor T1
open

Check the data in Error mode. Boiler data during error:
1 Error

= 36

2 Operational status = 00
3 Flow temp.

= -22

4 Return temp.

= xx*

5 kW burner

= 00**

6 % pomp

= xx*

* = variable values
**= x3415=BTU/hr
Check the wiring. check the wiring for the sensor

The wiring is OK but the error is repeated. Remove the plug from the fl ow
sensor as a result of which Error 31 occurs
Replace the sensor.