Installation & Servicing Instructions Rinnai E-Series

39

12" (300 mm)

minimum

12" (300 mm)

minimum

12" (300 mm)

minimum

INTAKE

EXHAUST

12" (300 mm)

minimum

12" (300 mm)

minimum

Terminal positions PVC figure 16

Equivalent friction loss of PVC/CPVC table 8

Fittings or Piping Equivalent

feet

m

45 degree elbow

3

0.91

90 degree elbow

6

1.83

plastic pipe per foot

1

0.30

concentric vent kit

5

1.52

6.7.5

Direct vent closet and alcove installation

For closet and alcove installation, CPVC material, instead of PVC, must be
used in a closet/alcove structure. Failure to follow this warning could result
in fi re, personal injury, or death.

Rinnai strongly suggests the use of concentric venting for all closet and
alcove installations. For non direct vent room air applications see sections
6.7.6 and 6.7.9.

!

WARNING

Closet installation

fi gure 17

Alcove installation

fi gure 18

2”

50mm

9”

229mm

8”

212.5mm

15”

386mm

6”

148mm

11”

268mm

10”

254mm

Closed door

1”(25mm) minimum clearance

around hot water pipes

1”(25mm) minimum clearance

around vent pipe

1”

25,4mm

2”

50mm

2”

50mm

9”

229mm

8”

212.5mm

6”

148mm

11”

268mm

10”

254mm

6”

152mm

Open front

1”(25mm) minimum clearance

around hot water pipes

1”(25mm) minimum clearance

around vent pipe

2”

50mm

15”

386mm