(10)To Close the SPECIAL2 (SPECIAL) Menu
Move the cursor to RET and press the CAM (SET) key.
The setup menu appears on the monitor screen.
Note:
How to Reset to the Factory Preset Parameters
Any of the above settings plus the ALC/MANUAL level control and
phase adjustments can be reset to the factory preset parameters by
placing the cursor over the desired mode and then press the F2 but
ton of the WV-CU550B.
(For the WV-RM70, keep pressing the Right and Left switches simul
taneously for 2 seconds or more.)
** SPECIAb2 “
CHROMA GAIN
AP GAIN
pESESTAb
HUE
• • • • I * * "
■ I .........
-
+
BW
OFF
BURST (BW)
OH
REFRESH
-tPUSH SW
CAMERA RESET
-iPUSB SW
DHR
LOW2
RET
■ RS485 Setup
• Initial Camera Communication Parameters
In an RS485 chain the matrix switcher, PC, controllers and cameras should be set to the same protocol
and parameters for communication.
Confirm the system protocol and parameters prior to setting the communication parameters for the cam
era.
The initial communication parameters for V\A/-CS854A are shown on the RS485 setup menu below.
Other than the on-screen-setup parameters, the 4-bit DIP switch may be used to select 2-line (Flalf
Duplex) or 4-line (Full Duplex) communication.
• Changing the Camera Communication Parameters
You can remote control this camera by using a specified extension unit such as a computer with a
modem.
1
.
2.
Display the SET UP MENU. Move the cursor to RS485 SET UP
and press the CAM (SET) key. RS485 SET UP menu appears on
the monitor.
Move the cursor to the item and select the parameter by moving
the joystick to the right or left.
RS485 Setup menu
** RS485 SET UP **
UHIT HUMBER
!n
SUB ADDRESS
1
BAUD RATE
19200
DATA BIT
8
PARITY CHECK
HOME
STOP BIT
1
XON/XOFF
HOT USE
WAIT TIME
OFF
ALARM DATA
AUT02
DELAY TIME
RET
OFF
UNIT NUMBER
Displays the unit number set by the DIP switch.
If the switch is set to 1-96, select a number by moving the joystick to the right or left.
In an RS485 chain each unit must have a unique number.
Default: 1. See INSTALLATION for DIP switch setting.
SUB ADDRESS
Do not set.
46