4 XM-124 Standard Dynamic Measurement Module

Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

Wiring Requirements

Use solid or stranded wire. All wiring must meet the following specifications:

14…22 AWG copper conductors without pretreatment; 8 AWG

required for grounding the DIN rail for electromagnetic interference
(EMI) purposes

Recommended strip length 8 mm (0.31 in.)
Minimum insulation rating of 300V
Soldering the conductor is forbidden
Wire ferrules can be used with stranded conductors; copper ferrules

recommended

Install the Module

To install the XM-124 Standard Dynamic Measurement Module, follow these
steps.

1. Mount the terminal base unit.

2. Wire the module.

3. Mount the module.

4. Connect the power supply.

5. Connect the channel outputs.

6. Establish a serial port connection.

7. Establish a DeviceNet connection.

ATTENTION: The XM-124 Dynamic Measurement Module is certified and
approved for use only in the 1440-TB-A/C terminal base unit. Do not install
the XM-124 module in any other terminal base unit.