Wiring Requirements
Use solid or stranded wire. All wiring must meet the following specifications:
• 14…22 AWG copper conductors without pretreatment; 8 AWG
required for grounding the DIN rail for electromagnetic interference
(EMI) purposes
• Recommended strip length 8 mm (0.31 in.)
• Minimum insulation rating of 300V
• Soldering the conductor is forbidden
• Wire ferrules can be used with stranded conductors; copper ferrules
recommended
Install the Module
To install the XM-124 Standard Dynamic Measurement Module, follow these
steps.
1. Mount the terminal base unit.
2. Wire the module.
3. Mount the module.
4. Connect the power supply.
5. Connect the channel outputs.
6. Establish a serial port connection.
7. Establish a DeviceNet connection.
ATTENTION: The XM-124 Dynamic Measurement Module is certified and
approved for use only in the 1440-TB-A/C terminal base unit. Do not install
the XM-124 module in any other terminal base unit.