10 XM-124 Standard Dynamic Measurement Module
Rockwell Automation Publication 1440-IN001B-EN-P - October 2013
21
Buffer/Xducer Pwr
(-)
Provides negative (-24...9V) voltage compliance to buffered outputs
Connect to terminals 5 (CH 1) and 22 (CH 2) for negative bias transducers
Transducer power supply output, negative side; used to power external
sensor (40 mA maximum load)
22
Buffer Power 2 IN
Channel 2 buffer power input
Connect to terminal 6 for positive bias transducers or terminal 21 for
negative bias transducers
23
CAN_High
DeviceNet bus connection, high differential (white wire)
24
CAN_Low
DeviceNet bus connection, low differential (blue wire)
25
+24 V Out
Internally connected to 24V In (terminal 44)
Used to daisy chain power if XM modules are not plugged into each other
If power is not present on terminal 44, there is no power on this terminal
26
DNet V (+)
DeviceNet bus power input, positive side (red wire)
27
DNet V (-)
DeviceNet bus power input, negative side (black wire)
28
24 V Common
1
Internally connected to 24V Common (terminals 43 and 45)
Used to daisy chain power if XM modules are not plugged into each other
29
4-20 mA 2 (+)
4...20 mA output
300
Ω maximum load
30
4-20 mA 2 (-)
31
Chassis
Connection to DIN-rail ground spring or panel mounting hole
32
Chassis
33
Chassis
34
Chassis
35
Chassis
36
Chassis
37
Chassis
38
Chassis
39
SetPtMult
Switch input to activate Set Point Multiplication (active closed)
40
Switch RTN
Switch return, shared between SetPtMult and Reset Relay
Terminal Block Assignments
No.
Name
Description