16 XM-124 Standard Dynamic Measurement Module
Rockwell Automation Publication 1440-IN001B-EN-P - October 2013
Connect the DeviceNet cable to the terminal base unit as follows.
DeviceNet Cable Connections
Connect
To
Terminal
Red wire
DNet V+
26 (optional)
White wire
CAN High
23
Bare wire
Shield (Chassis)
10
Blue wire
CAN Low
24
Black wire
DNet V-
27
IMPORTANT The DeviceNet power circuit through the XM module interconnect, which is rated
at only 300 mA, is not intended or designed to power DeviceNet loads. Doing so
could damage the module or terminal base unit.
IMPORTANT
the XM-124 Standard Dynamic Measurement Module User Manual, publication
1440-UM001
.
ATTENTION: You must ground the DeviceNet shield at only one location.
Connecting the DeviceNet shield to terminal 10 grounds the DeviceNet
shield at the XM module. If you intend to terminate the shield elsewhere, do
not connect the shield to terminal 10.
ATTENTION: The DeviceNet network must also be referenced to earth
ground at only one location. Connect DNet V- to earth ground or chassis at
one of the XM modules.