XM-124 Standard Dynamic Measurement Module 13

Rockwell Automation Publication 1440-IN001B-EN-P - October 2013

Connect the Power Supply

Power supplied to the module must be 24V DC nominally (±10%) and must be
a Class 2 rated source.

Wire the DC-input power supply to the terminal base unit as shown below.

DC Input Power Supply Connection

IMPORTANT

A Class 2 circuit can be provided by use of an NEC Class 2 rated power
supply, or by using a SELV or PELV rated power supply with a 5 A current
limiting fuse installed before the XM module.

IMPORTANT

24V DC must be wired to terminal 44 (+24V In) to provide power to the
device and other XM modules linked to the wired terminal base unit via
the side connector.

ATTENTION: The power connections vary for different XM modules. Refer to
the installation instructions for your specific XM module for complete wiring
information.