Horizontal Vent Termination- 75mm (3") Concentric PVC/CPVC Termination

Hanger

Straps

The concentric termination may be shortened,
but not lengthened from its original factory
supplied length.

Terminate at least 300mm (12") above grade or
above snow line.

Terminate at least 2.1m (7') above a public walkway,
1.8m (6') from the combustion air intake of
any appliance, and 0.9m (3') from any other
building opening, gas utility meter, service
regulator etc.

Teminate at least 0.9m (3') above any forced air
inlet within 3m (10'), 1.2m (4') below, 1.2m (4')
horizontally from or 0.3m (1') above any door,
window, or gravity air inlet into any building per
National Fuel Gas Code ANSI Z223.1/NFPA 54.

Slope the horizontal vent 1/4" upwards
for every 300mm (12").

Use a condensation drain if necessary.

In the Commonwealth of Massachusetts
a carbon monoxide detector is required
for all side wall horizontally vented gas
fuel equipment. Please refer to Technical
Bulletin TB 010606 for full installation in
structions.

75mm (3")
Intake

75mm (3")
Exhaust

PVC/CPVC

Adapter*

PVC/CPVC

Coupling

* Not supplied with water
heater, order separately.

Slope vent
Upwards

25mm (1")
Minimum

Pipe diameter

No. of Elbows

3

3m (10')

2

3.9m (13')

1

4.8m (16')

Insert Bird Screen
in End of Termination

**Not including the concentric termination

There must be a minimum of 25mm (1") clearance
between the outside wall and the air intake section
of the termination as illustrated on the left.

Install a securing strap to prevent movement of
the termination.

Strap

Max. Straight Vent Length**

75mm (3") PVC or CPVC