Vent pipe installation, Danger – John Wood Noritz Condensing - N-0841MC Manuel d'utilisation
Page 47

47
8.
Vent Pipe Installation
(Indoor Installation Only)
Vent Terminal Installation
• Follow the installation instructions included with the vent terminal. It is suggested that the appliance be
vented horizontally through a sidewall. If a vertical vent termination is required, it must follow the
requirements of this section (p.49-52).
Filling the neutralizer unit with water
The neutralizer unit can be filled before connecting the vent pipe.
Filling the neutralizer unit before vent pipe installation.
DANGER
Prior to initial start up, make sure that you fill the neutralizer unit with water.
This is to prevent dangerous exhaust gases from entering the building.
Failure to fill the neutralizer unit could result in severe personal injury or death.
Please follow one of the procedures described below to ensure that the neutralizer unit is filled with water.
1) Fill the neutralizer unit by pouring approx. 17 oz.(500ml) of water into the exhaust accessory on the top of
the appliance as illustrated below.
Or, if the vent pipe has already been installed:
2) After installing the drain pipe, make sure that the area around the appliance is well ventilated; open a
window or a door if necessary.
Then, operate the unit and verify that condensate is coming out of the drain pipe.
(During normal use of the water heater, condensate will begin to discharge from the drain pipe within 15 minutes
of use. However, depending on the season and/or installation site conditions, it may take longer.)
17 oz.
500ml
Vent Terminal Installation Precautions
Note the following vent terminal installation requirements
• Do not install the vent terminal indoors
• Install the vent terminal with a downward slope
upward
slope
downward
slope
Intake
Exhaust