Before installation, Danger, Warning caution – John Wood Noritz Condensing - N-0841MC Manuel d'utilisation

Page 41

Advertising
background image

41

4.

Before Installation

Checkup

• Check the fixing brackets and vent pipe yearly for damage or wear. Replace if necessary.

DANGER

Do Not Use Equipment for Purposes Other Than Those Specified

• Do not use for other than increasing the temperature of the water supply, as unexpected accidents

may occur as a result.

Check Water Supply Quality

• If the water supply is in excess of 12 grains per gallon (200 mg/L) of hardness, acidic or otherwise

impure, treat the water with approved methods in order to ensure full warranty coverage.

WARNING

CAUTION

Check the Gas

• Check that the rating plate indicates the

correct type of gas.

• Check that the gas supply line is sized for

199,900 Btuh for this unit.

Check the Power

• The power supply required is 120VAC, at 60Hz.

May result in fire or electric shock.

Use Extreme Caution if Using With a Solar Pre-Heater

• Using this unit with a solar pre-heater can lead to unpredictable output temperatures and
possibly scalding. If absolutely necessary, use mixing valves to ensure output temperatures do

not get to scalding levels. Do not use a solar pre-heater with the quick-connect multi-system.

Precautions on Vent Pipe Replacement

• The vent system will almost certainly need to be replaced when this appliance is being installed.

Use vent pipe that is listed to UL 1738 for Category IV appliances for the exhaust venting. Category
IV listed vent pipe is suggested for the air supply pipe also, but other materials may be acceptable.
Consult local codes.
* If Category IV listed vent pipe is already installed, check for punctures, cracks or blockages and

consult with the vent pipe manufacturer before reusing.

Use Approved Vent Materials

• Use only vent materials that are listed to UL 1738 for Category IV appliances for the exhaust venting

of this appliance.
Improper venting may result in fires, property damage or exposure to Carbon Monoxide.

Snow Precaution

• If this product will be installed in an area where snow is known to accumulate, protect the vent

termination from blockage by snow drifts or damage from snow falling off of roofs.

199,900

199,900

186,000

186,000

3.6

3.35

3.35

3.6

192,700

192,700

179,300

179,300

199,900 BTU

11,000 BTU

222

4.0

0.75

3.35

10.5

840

10.3a-2007

15

150

4.3a-2007

4

N-0841MC-DV

Advertising