John Wood Noritz Condensing - N-0841MC Manuel d'utilisation

Page 33

Advertising
background image

33

G

(1 1/4"-2")

Unit 6

Unit 2

Unit 1

System Controller

Storage tank supply line

(1 1/4"-2")

Storage tank return line

(Copper or Stainless Pipe)

(Copper or Stainless Pipe)

Storage Tank Circulation Pump 1

Storage Tank Circulation Pump 2

(if Necessary)

Gas Pipe

Hot Water

Storage Tank

Relief Valve

Hot water supply line

(Copper or Stainless Pipe)

Return line

circulation pump

Hot water return line

(Copper or Stainless Pipe)

Cold Water Supply

* Size the water supply piping to

allow for maximum flow rates

of the building.

* Set dipswitch 3 to OFF.

(See SC-201-6M Installation Manual)

* If the tank thermostat will control the pump

set dipswitch 2 to OFF.

(See SC-201-6M Installation Manual)

Do not connect more than one pump to the

tank thermostat.

Hot Water

Supply

Remote

Controller

Option 2-Unit

Control

Option 1-Tank

Thermostat Control

When installing 2 pumps in parallel

The system controller will stop the units from heating when the tank is up to temperature,

and the unit will cut the flow through it to 9.8 L/min. (2.6 GPM).

Install the plumbing so that a change in flow will not damage the pump.

Thermostat

System select connector

Connect to the “Sto-

rage system”

connector"

Pump Control

Wires (use

external relay)

* Also

disconnect this

connector on units 2-6

Disconnect this Connector

B-2. Example of Installation with a Storage Tank and Recirculation System

The pump will push water through the Multi-System to heat up the tank.
When the return temperature is high, the flow within the device will be limited to 9.8 L/min. (2.6 GPM)*.

*

For the set temperature of the remote control, use the temperature (of the thermostat) + about 6

°C (10

°F).

*

To achieve the highest recovery, size the storage tank circulation pump for maximum capacity.

( 34 L/min. (9 GPM) (each) @ 120kPa (40 ft.) of head (71

°C (160

°F) setting or less) + piping losses through the system).

Verify the supply pressure to the units is at least 30 PSI.