Vertical Vent Termination

• Terminate at least 1.8m (6') from

the combustion air intake of any
appliance, and 0.9m (3') from any

other building opening, gas utility

meter, service regulator etc.

• Enclose exterior vent systems

below the roof line to limit conden-
sation and protect against me-
chanical failure.

• When the vent penetrates a floor

or ceiling and is not

running in a fire rated shaft, a

firestop and support is required.

• Terminate the vent system at least

0.6m (2') above, but not more than
1.8m (6') above the roof line, or
according to the vent pipe
manufacturer's instructions.

• Provide vertical support every

3.6m (12') or as required by the
vent pipe manufacturer's instructions.

• Slope the horizontal vent 1/4"

downwards for every 300mm (12").

• Do not vent straight upwards.

Always have a horizontal section of
venting.

• Install a condensation drain in the

horizontal section of the venting.

Appliance

Adapter

Firestop

Firestop/

Support

Roof

Flashing

RainCap

Exhaust

Intake Air

Hanger

Strap

Elbow

Condensation

Drain (Install
According to

Local Codes)

0.3 - 0.6m
(1-2')

1.8m (6')

0.6m (2')

Min.

* Adapter not required when
using Noritz N-Vent.

Roof

Jack

Storm

Collar

**0.3m (1') Min. -
0.9m (3') Max.

** 0.3m (1') minimum recommended,
but not required. Avoid installing
elbow directly on flue.

(Combustible material)

Intake pipe

External wall,
combustible material

• Inspection openings are suggested for the vent intake and exhaust

pipes if they are installed in an enclosure. These openings should
be near the entrance and exit of the vent into the enclosure.

• These openings should be 450mm x 450mm (18" x 18").

Suggested inspection openings

450mm x 450mm (18" x 18")

When the intake/exhaust pipes pass through an enclosed space:

Ceiling

Sloping down toward vent terminal

Exhaust pipe