Vertical Vent Termination

Firestop

Firestop/

Support

Roof

Flashing

Roof

Jack

Storm

Collar

Rain

Cap

Hanger

Strap

Elbow

Condensation

Drain (Install
According to

Local Codes)

Appliance

Adapter*

* Adapter not required when
using Noritz N-Vent.

**0.3m (1') Min. -
0.9m (3') Max.

** 0.3m (1') minimum recommended,
but not required. Avoid installing
elbow directly on flue.

• Terminate at least 1.8m (6') from the combus-

tion air intake of any appliance, and 0.9m (3')
from any

other building opening, gas utility

meter, service regulator etc.

• Enclose exterior vent systems below the roof

line to limit condensation and protect against
mechanical failure.

• When the vent penetrates a floor or ceiling and

is not running in a fire rated shaft, a firestop and
support is required.

• Terminate the vent system at least 0.6m (2')

above, but not more than 1.8m (6') above the
roof line, or according to the vent pipe
manufacturer's instructions.

• Terminate the vent system at least 0.6m (2')

above any portion of a building located within
3m (10') horizontally.

• Provide vertical support every 3.6m (12') or as

required by the vent pipe manufacturer's in-
structions.

• Slope the horizontal vent 1/4" for every 300m

(12") towards the drain tee.

• Do not vent straight upwards.

Always have a horizontal section of venting.

• Install a condensation drain in the horizontal

section of the venting.

Horizontal Vent Termination

• Terminate at least 300mm (12") above

grade or above snow line.

• Terminate at least 2.1m (7') above a public

walkway, 1.8m (6') from the combustion air
intake of any appliance, and 0.9m (3') from
any other building opening, gas utility meter,
service regulator etc.

• Terminate at least 0.9m (3') above any

forced air inlet within 3m (10'), 1.2m (4') be-
low, 1.2m (4') horizontally from or 0.3m (1')
above any door, window, or gravity air inlet
into any building per National Fuel Gas Code
ANSI Z223.1/NFPA 54.

• Slope the horizontal vent 1/4" downwards

for every 300m (12").

• Use a condensation drain if necessary.
• In the Commonwealth of Massachusetts a

carbon monoxide detector is required for all
side wall horizontally vented gas fuel equip-
ment. Please refer to Technical Bulletin TB
010606 for full installation instructions.

Appliance

Adapter*

Elbow

Hanger

Straps

Wall

Thimble

Termination

**0.3m (1') Min. -
0.9m (3') Max.

Slope vent

Downwards

* Adapter not required when
using Noritz N-Vent.

** 0.3m (1') minimum recommended,
but not required. Avoid installing
elbow directly on flue.