Maintain the following clearances to any

opening in any building:

Illustration

* For Installations in Canada, clearances are as follows: To windows, doors, & gravity air inlets: 900mm (36").

To forced air inlets: 1.8m (6').

Outdoor Clearances to Opening

into Any Building

• 0.3m (1') below, 0.3m (1') horizontally from,

or 0.3m (1') above any door, operable
window, or gravity air inlet into any building.
0.9m (3') above any forced air inlet within
3m (10').

Vent Clearances When Heater is

Installed in a Recess Box

(recess box installation with cover removed)

0.3m (1')

0.9m (3')

0.3m
(1')

0.3m
(1')

[ For N-0931M- OD]

• 0.3m (1') below, 0.3m (1') horizontally from,

or 0.3m (1') above any door, operable
window, or gravity air inlet into any building.
0.9m (3') above any forced air inlet within
3m (10').

0.9m (3')

0.3m (1')

0.3m (1')

0.3m
(1')