Chapter 1. Introduction

Following the protective function letters is a two-character

code indicating the type of target module installed (if

any), as listed in Table 4.

Suffix Target Module Cat. No.

(none) TARGET00

(blank)

T2

TARGET02 (with GF)

Table 4. Control Unit catalog number code indicating the

Target Module installed.

Finally, if the Control Unit was ordered as a replacement,

the letter “R” is appended to the catalog number.
For example, a Control Unit with catalog number

D220T2R has the following functions:

D – Control Unit for Power Break II switch
2 – Maximum CT rating of 2000 A
20 – Switch current sensor (CT) of 2000 A
T2 – Target module with ground-fault trip indication
R – Control Unit was ordered as a replacement

1–5 Rating Plugs

A rating plug, shown in Figure 1, is supplied in the switch

with a rating coordinated to that of the current sensor. A

rating plug must be replaced only with a unit with the

identical rating.

Figure 1. Power+ rating plug shown with ground-fault

protection function.

Ground-Fault Protection

Ground-fault protection with Power+ Control Units is pro-

vided as an option in the rating plug. Ground-fault

protection is activated by installing a rating plug with the

ground-fault option into the Control Unit. The pickup

and delay settings available with the switches on the rating

plug are described in Chapter 2,

Control Unit Setup

.

To order a rating plug with the ground-fault protection

function, append “GF” to the catalog number of the rating

plug with the desired sensor and plug rating.

WARNING:

Rating plugs equipped with ground fault

must be replaced only with other ground-fault-equipped

rating plugs. Failure to do so could result in personal

injury or death, as well as damage to equipment.

AVERTISSEMENT:

Les calibreurs munis d’un détecteur

de défaut de mise à la terre ne doivent être remplacés

que par des calibreurs munis d’un détecteur de défaut de

mise à la terre. La non application de cette directive peut

entraîner des blessures ou même provoquer la mort ainsi

qu’endommager l’équipment.

1–6 Equipment Interfaces

Power+ Control Units do not usually require connections

within the equipment, since all wiring is contained within

the switch. The only connection is for the neutral sensor,

which uses a special dedicated disconnect.

CAUTION:

Neutral current sensors are required for sin-

gle-phase, three-wire and three-phase, four-wire systems.

When the Control Unit is connected to a three-phase,

three-wire system, the neutral sensor terminals of the

switch are left open. Do not short any neutral current

sensor terminals in a three-phase, three-wire system, as

this could result in damage to, or malfunction of, the

electrical system.

ATTENTION:

Des capteurs de courant de neutre sont

nécessaires pour les systèmes à phase simple, trois câbles

et trois phases, quatre câbles. Lorsque l'unité de contrôle

est branchée à un système trois phases, trois câbles, les

terminaux de capteur de neutre de l'interrupteur sont

laissés ouverts. Ne court circuiter aucun des terminaux

de capteur de courant de neutre dans un système trois

phases, trois câbles, car il pourrait résulter en des

dommages ou un mauvais fonctionnement du système

électrique.