Table 5. summary of ground-fault trip settings, Power+™ control units, 2–1 overview – GE Industrial Solutions Power Plus Control Units Manuel d'utilisation
Page 10: 2–2 ground-fault pickup, 2–3 ground-fault delay, Chapter 2. control unit setup

Power+™ Control Units
Chapter 2. Control Unit Setup
2–1 Overview
Both of the Control Unit protective functions are set with
the rotary selector switches on the front of the rating plug.
Table 5 contains a summary of the functions and the
available settings.
2–2 Ground-Fault Pickup
This function sets the pickup current for ground-fault
protection. The available settings are .2, .25, .3, .35, .4, .45,
.5, and .6 times the current sensor rating,
S
. The
maximum setting may be less than .6, depending on the
switch frame size. Figure 2 illustrates the time-current
curve for ground-fault pickup.
Current
Ground-Fault
Pickup Settings
Figure 2. Time-current curve illustrating ground-fault pickup.
2–3 Ground-Fault Delay
This function sets the delay before the switch opens when
the ground-fault pickup current is detected. The switch
settings
MIN
,
INT
, and
MAX
correspond to nominal time
delays of .10, .21, and .35 second, respectively. The delay
with
I
2
T OUT
is for the lower limit of each band. The delay
with
I
2
T IN
is at 200% of the pickup setting at the lower
limit of the band.
The
I
2
T OUT
function, illustrated in Figure 3, establishes a
constant time delay.
I
2
T IN
biases the delay with a constant
slope, as shown in Figure 4.
Current
Delay Set Points
with I T OUT
2
Figure 3. Time-current curve illustrating ground-fault delay
with I
2
T OUT.
Current
Delay Set Points
with I
2
T IN
Figure 4. Time-current curve illustrating ground-fault delay
with I
2
T IN.
Parameter
Pickup Settings
Delay Settings
Delay Curve
Ground-Fault Trip
.2, .25, .3, .35, .4, .45, .5, .6*
multiple of Sensor rating (S)
.10, .21, .35 seconds
(Min, Int, Max)
I
2
T In, I
2
T Out
* Maximum setting is limited by the frame size.
Table 5. Summary of ground-fault trip settings.
4