3–1 overview 3–2 functions, Trip targets battery test health monitor, Figure 5. target module – GE Industrial Solutions Power Plus Control Units Manuel d'utilisation

Page 11: Table 6. target module catalog numbers, Power+™ control units, 3–1 target module, 3–2 functions, Chapter 3. control unit status, Trip targets, Battery test

Advertising
background image

Power+™ Control Units

Chapter 3. Control Unit Status

3–1 Target Module

Control Unit status information is provided by the

optional target module. This module indicates when a

switch opening was caused by a ground fault, as well as

whether the Control Unit is functioning properly. The

target module is shown in Figure 5.
If a Control Unit is ordered without a target module, a

blank insert is installed in the Control Unit slot. Catalog

numbers are listed in Table 6.

NOTE:

The target modules that include ground-fault

trip indication do not provide the ground-fault

protection function. If ground-fault protection is

required, a ground-fault-equipped rating plug must be

installed in the Control Unit.

NOTE:

Les modules à voyants lumineux (target) qui

incluent une indication de déclenchement d’un défaut

de mise à la terre ne sont pas équipés d’un fonction de

protection d’un défaut de mise à la terre. Si une telle

fonction est requise, un calibreur mini d’une fonction de

protection d’un défaut de mise à la terre doit être installé

dans l'unité de contrôle.

Figure 5. Target module.

Catalog No.

Description

TARGET00 Blank

insert

TARGET02

With ground fault target

Table 6. Target Module catalog numbers.

3–2 Functions

The front of the target module contains two push buttons

and either four or five LEDs. The following functions are

provided by the target module.

Trip Targets

To verify the condition causing a switch trip, press the

VIEW

button. The GF LED will light. The

RESET

button

clears the trip target indication.

Battery Test

If the switch has not tripped or if the trip target has been

cleared, pressing the

VIEW

button performs a battery test.

The

BAT

LED will light if the batteries are okay. If the

BAT

LED is dim or does not light, replace the Control Unit

batteries as described in Chapter 4,

Maintenance and

Trouble-Shooting

. Note that the only function of the

Target Module batteries is to power the LEDs; they have

no effect on Control Unit operation and are not required

to store targets or for ground fault functions.

Health Monitor

The Control Unit can be tested for proper functioning if

the Control Unit is powered by one of the following

sources:

• A Test Kit (catalog number TVRMS2) is plugged

into the jack on the front of the Rating Plug.

• The switch is carrying a load current of at least 20%

of its current sensor rating.

• External +24 Vdc control power is connected.

Press and hold the

VIEW

button for at least five seconds. If

the Control Unit is operating properly, the

LTPU

LED will

blink slowly. Note that if the Control Unit is not powered

by one of the above sources, this test will not give a true

indication of Control Unit functioning.

5