Power+™ Control Units

Chapter 4. Maintenance and Trouble-Shooting

4–4 Trouble-Shooting Guide

The following guide is provided for trouble-shooting and

isolating common problems. It does not cover every possi-

ble condition. Contact the Customer Support Center at

800-843-3742 if the problem is not resolved by these pro-

cedures.

Symptom Possible

Cause

Corrective

Action

1. The health monitor

function of the optional

target module does not

operate.

Line current is below 20% of

the switch sensor rating.


The target module is not

seated properly.

At least 20% of the current sensor rating,

X

, must be

flowing through the switch to activate this function. If

the load current is below this level, power the Control

Unit with the Test Kit or the Portable Power Pack.
Verify that the target module is fully seated in its slot.

2. The trip indication

target will not clear.

The target module batteries

are low.

Replace the batteries in the target module.

3. The battery check

(

BAT

) LED on the

target module does not

light.

The target module batteries

are low.

Replace the batteries in the target module