Power+™ Control Units

Chapter 1. Introduction

1–1 Applications

The Power+™ Control Units described in this publication

are used on Power Break® II insulated-case switches.

1–2 General

Power+ Control Units are the same size and have the same

connectors as the Power+ trip units and the RMS9D series

of MicroVersaTrip Plus™ and MicroVersaTrip PM™ trip

units.
Power+ Control Units may be tested with the Control Unit

installed in the switch, the rating plug installed in the

Control Unit, and the switch carrying current. The Test

Kit plugs into the test socket of the rating plug. The Test

Kit catalog number is TVRMS2 and its operation is

described in GEK–97367.
Power+ Control Units are removable from the switch. For

instructions on installing and removing the Control Unit,

see Chapter 4 of this guide or the appropriate switch

user’s guide.

CAUTION:

Removal of a Control Unit from its switch

must be performed with the switch in the

OPEN

or

TRIPPED

position. Draw-out switches should be racked

out first.

ATTENTION:

Pour retirer unité de contrôle,

l'interrupteur doit être en position ouverte ou

déclenchée. Les interrupteurs débrochables doivent ètre

en position débrochée.

CAUTION:

Do not attempt to operate the switch without

its assigned Control Unit. Installation of an incorrect

Control Unit may result in unsafe operation of the

switch.

ATTENTION:

Ne pas tenter d'opérer l'interrupteur sans

son unité de contrôle assignée. L'installation d'une unité

de contrôle incorrecte peut avoir comme conséquence

une opération non sécuritaire de l'interrupteur.

NOTE:

Control Units as received may have settings that

are undesirable for the specific application. Ensure that

settings are appropriately adjusted before energizing.

NOTE:

Unités de contrôle sont livrés avec des réglages

standards qui peuvent être inadéquates pour certaines

applications. Vérifier ces réglages avant de mettre le

disjoncteur sous tension.

1–3 Control Unit Functions

Power+ Control Units have specific standard and optional

functions. The standard function of the Control Unit is to

operate switch accessories.
The optional functions available are as follows:

• Protection

– Ground-fault protection, with or without I

2

T

• Status

– Ground-fault trip targets
– Health monitor

1–4 Control Unit Catalog Numbers

A simple catalog-numbering system defines all of the stan-

dard and optional Control Unit functions. A complete

catalog numbering key is found inside the front cover.

Each of the segments of the catalog number is described

below.
The first character indicates the switch type for which the

Control Unit is configured, as listed in Table 1.

Character Switch

Type

D

Power Break II

Table 1. Switch type referred to by the first character of the

Control Unit catalog number.

The second character of the catalog number indicates the

highest-rated current transformer (CT) sensor allowed for

that switch frame, as listed in Table 2.

Character Maximum

CT

2 2000

A

3 3000

A

4 4000

A

Table 2. Highest-rated CT allowed in the switch frame, given

by the second character of the Control Unit catalog number.

The third and fourth characters of the catalog number

indicate the CT that is actually installed in the switch, as

listed in Table 3.

Characters Installed

CT

08 800

A

16 1600

A

20 2000

A

25 2500

A

30 3000

A

40 4000

A

Table 3. Installed CT, as indicated by the third and fourth

characters of the Control Unit catalog number.

1