16

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

SUPERIOR

®

B-VENT GAS FIREPLACES • MODELS SLBV-35, SLBV-40 • CARE AND OPERATION INSTRUCTIONS

WARNING

Air shutter adjustment should

only be performed by a quali-

fied professional service

technician.

Ensure front glass panel are

in place and sealed during

adjustment.

CAUTION

Soot will be produced if the

air shutter is closed too much.

Any damage due to carboning

resulting from improperly

setting the air shutter is not

covered under the warranty.

The air shutter door and nearby

appliance surfaces are hot.

Exercise caution to avoid

injury while adjusting flame

appearance.

Burner Air Shutter Adjustment

Procedure

Electronic Appliance Checkout

To light the burner, refer to the lighting instruc-

tions on Page 24. Ensure the igniter lights the

pilot. The pilot flame should engulf the flame

sensor as shown in Figure 15.

APPLIANCE CHECKOUT

Millivolt Appliance Checkout

The pilot flame should be steady, not lifting

or floating. Flame should be blue in color with

traces of orange at the outer edge.

The top 3/8" (10 mm) at the pilot generator

(thermopile) and the top 1/8" minimum (tip)

of the quick drop out thermocouple should be

engulfed in the pilot flame. The flame should

project 1" (25 mm) beyond the hood at all three

ports (see Figure 14).

To light the burner, refer to the lighting instruc-

tions on Page 22.

Thermocouple

Thermopile

Pilot

Nozzels

SIT MILLIVOLT PILOT ASSEMBLY

3/8" Min.

(9 mm)

Igniter Rod

Pilot Hood

Proper Pilot Flame Appearance

Figure 14

1. Locate adjustment rod and adjust air shutter

to the standard setting as shown in Figure

13 (adjustment rod is located in the lower

control compartment).

Note: Move the adjustment rod DOWN

to decrease air and UP to increase air.

2. Light appliance (follow lighting procedure

on lighting label in control compartment or

see the lighting instructions on Pages 22

and 22 in this manual).

ELECTRONIC PILOT ASSEMBLY

ELECTRONIC

Pilot

Hood

Sensor

Igniter

Figure 15

Burner Air Shutter Adjustment

Figure 13

Adjustment

Rod Up

(Fully Open

Position)

Air Shutter

Adjustment Rod Down min.

air opening position)

Burner

Tube

Adjustment Set-Screw

3. Allow the burner to operate for at least 15 min-

utes while observing the flame continuously

to ensure that the proper flame appearance

has been achieved (see Figures 11 and 12 on

previous Page). If the following conditions

are present, adjust accordingly.

• If flame appears weak or sooty, adjust

the air shutter, incrementally, to a more

open position until the proper flame

appearance is achieved.

• If flame stays lowered blue, adjust the

air shutter, incrementally, to a more

closed position until the proper flame

appearance is achieved.

4. Leave the control knob (off/pilot/on) in the

ON position and the burner OFF/ON switch

OFF (and remote switches, if applicable).

5. When satisfied that the burner flame ap-

pearance is normal, close the lower control

compartment door (see Figures 11 and 12

on previous Page).

Main Burner Factory Air Shutter

Opening Setting

inches (millimeters)

Model

Natural

Gas

Propane

Gas

SLBV-35

Closed

3/32

(2.362)

SLBV-40

Closed

3/32

(2.362)