7.0 ADJUSTMENTS

Remove the pilot screw cap. Adjust the pilot screw to provide properly
sized fl ame. Turn in a clockwise direction to reduce the gas fl ow.
Re-install the pilot screw cap.

Inlet pressure can be checked by turning screw (A)
counter-clockwise until loosened and then placing pressure
gauge tubing over the test point. Gauge should read 7”
(minimum 4.5”) water column for natural gas or 13” (11” minimum)
water column for propane. Check that main burner is operating on “HI”.

Outlet pressure can be checked the same as above using screw (B).
Gauge should read 3.5” water column for natural gas or 10” water
column for propane. Check that main burner is operating on “HI”.

AFTER TAKING PRESSURE READINGS, TIGHTEN
SCREWS FIRMLY TO SEAL. DO NOT OVER
TORQUE. LEAK TEST.

39.6

PILOT

BURNER

THERMOCOUPLE

THERMOPILE

PI

L

O

T

PILOT SCREW

A

B

7.1 VENT

RESTRICTION

7.2 PILOT BURNER ADJUSTMENT

Vertical terminations running longer than fi fteen feet may display a
very active fl ame. When this is not desirable, a vent restrictor could
be installed. This restrictor plate will reduce the velocity of the exhaust
gases, slowing down the fl ame pattern and creating a more traditional
appearance.

A.

Remove the glass viewing door and logs.

B.

Secure the restrictor plate as described.

C.

Replace logs and viewing door.

Line up the holes on the vent restrictor with the holes on the bracket
attached to the roof of the fi rebox.

Secure the vent restrictor into position using the two screws supplied.