Warning – Napoleon Fireplaces GDI44 Manuel d'utilisation

Page 10

Advertising
background image

10

W415-0734 / D / 02.03.12

3.3 GAS

INSTALLATION

3.4 OPTIONAL ACCESSORY REQUIREMENTS

A.

This appliance may be used with a wall switch, wall mounted thermostat and/or a remote control.

B.

Wiring for optional Napoleon® approved accessories should be done now to avoid reconstruction.

Follow instructions that come with those accessories.

For ease of accessibility, an optional remote wall switch or millivolt thermostat may be installed in a convenient
location. Route 2-strand solid core millivolt wire from the gas appliance to the wall switch / millivolt thermostat.
The recommended maximum lead length depends on the wire size:

WIRE SIZE

MAX. LENGTH

14gauge

100

feet

16gauge

60 feet

18gauge

40

feet

Do not connect either the wall switch, thermostat or gas valve to electricity (110 VOLTS).

30.1A

Installation and servicing to be done by a qualifi ed installer.
A.

Move the appliance into position and secure.

B.

If equipped with a fl ex connector the appliance is designed to accept a 1/2” gas supply. Without the
connector it is designed to accept a 3/8” gas supply. The appliance is equipped with a manual shut off
valve to turn off the gas supply to the appliance.

C.

Connect the gas supply in accordance to local codes. In the absence of local codes, install to the
current CAN/CSA-B149.1 Installation Code in Canada or to the current National Fuel Gas Code, ANSI
Z223.1 / NFPA 54 in the United States.

D. When

fl exing any gas line, support the gas valve so that the lines are not bent or kinked.

E.

The gas line fl ex-connector should be installed to provide suffi cient movement for shifting the burner
assembly on it’s side to aid with servicing components.

F.

Check for gas leaks by brushing on a soap and water solution. Do not use open fl ame.

!

WARNING

RISK OF FIRE, EXPLOSION OR ASPHYXIATION. ENSURE THERE ARE NO IGNITION SOURCES SUCH AS

SPARKS OR OPEN FLAMES.

SUPPORT GAS CONTROL WHEN ATTACHING GAS SUPPLY PIPE TO PREVENT DAMAGING GAS LINE.

ALWAYS LIGHT THE PILOT WHETHER FOR THE FIRST TIME OR IF THE GAS SUPPLY HAS RUN OUT

WITH THE GLASS DOOR OPENED OR REMOVED. PURGING OF THE GAS SUPPLY LINE SHOULD BE

PERFORMED BY A QUALIFIED SERVICE TECHNICIAN. ASSURE THAT A CONTINUOUS GAS FLOW IS AT

THE BURNER BEFORE CLOSING THE DOOR. ENSURE ADEQUATE VENTILATION. FOR GAS AND

ELECTRICAL LOCATIONS, SEE “DIMENSION” SECTION.

ALL GAS CONNECTIONS MUST BE CONTAINED WITHIN THE APPLIANCE WHEN COMPLETE.

HIGH PRESSURE WILL DAMAGE VALVE. DISCONNECT GAS SUPPLY PIPING BEFORE TESTING GAS

LINE AT TEST PRESSURES ABOVE 1/2 PSIG.

VALVE SETTINGS HAVE BEEN FACTORY SET, DO NOT CHANGE.