Symptom problem test solution – Napoleon Fireplaces Grandville 36 - BGD36 Manuel d'utilisation

Page 58

Advertising
background image

58

W415-0773 / F / 08.26.13

EN

SYMPTOM

PROBLEM

TEST SOLUTION

Pilot will not light.

No spark at pilot burner.

-

Check if pilot can be lit by a match.

-

Check that the wire is connected to the push button igniter.

-

Check if the push button igniter needs tightening.

-

Replace the wire if the wire insulation is broken or frayed.

-

Replace the electrode if the ceramic insulator is cracked
or broken.

-

Replace the push button ignitor

Out of propane gas.

-

Fill the tank.

Spark gap is incorrect.

-

Spark gap should be 0.150” (3.8mm) to 0.175” (4.5mm)
from the electrode tip and the pilot burner. To ensure
proper electrode location, tighten securing nut (fi nger
tight plus 1/4 turn).

No gas at the pilot burner.

-

Check that the manual valve is turned on.

-

Check the pilot orifi ce for blockage.

-

Replace the valve.

-

Call the gas distributor.

Flames are consistently
too large or too small.
Carboning occurs.

Unit is over-fi red or underfi red.

-

Check pressure readings:

-

Inlet pressure can be checked by turning screw (A)
counter-clockwise 2 or 3 turns and then placing pressure
gauge tubing over the test point. Gauge should read as
described on the chart below.

Check with main burner is

operating on ‘HI’.

-

Outlet pressure can be checked the same as above
using screw (B). Gauge should read as described on the
chart below. Check that main burner is operating on ‘HI’.

-

AFTER TAKING PRESSURE READINGS, BE SURE TO
TURN SCREWS CLOCKWISE FIRMLY TO RESEAL.
DO NOT OVER TORQUE.

-

Leak test with a soap and water solution.

-

Flames are very aggressive.

Door is ajar.

-

Ensure the mechanical means of securing the door is
providing a tight seal.

Venting action is too
great.

-

Check to ensure venting is properly sealed.

-

If restriction is required see “RESTRICTING VERTICAL
VENT” section.

Carbon is being
deposited on glass, logs
or combustion chamber
surfaces.

Air shutter has become
blocked.

-

Ensure air shutter opening is free of lint or other
obstructions.

Flame is impinging on the logs
or combustion chamber.

-

Check that the logs are correctly positioned.

-

Open air shutter to increase the primary air.

-

Check the input rate: check the manifold pressure and
orifi ce size as specifi ed by the rating plate values.

-

Check that the door gasketing is not broken or missing
and that the seal is tight.

-

Check that both vent liners are free of holes and well
sealed at all joints.

-

Check that minimum rise per foot (meter) has been
adhered to for any horizontal venting.

42.3_2E

P

I

PILOT

N

O

L

O

T

H

I

L O

F

F O

A

B

PILOT

BURNER

THERMOCOUPLE

THERMOPILE

Pressure

Inlet

Outlet

Natural Gas

(inches)

Natural Gas

(millibars)

Propane

(inches)

Propane

(millibars)

7"

(MIN. 4.5")

3.5"

13"

(MIN. 11")

10"

17.4mb

(MIN. 11.2mb)

8.7mb

32.4mb

(MIN. 27.4mb)

24.9mb

Advertising
Ce manuel est liée aux produits suivants: