3.10 TOP OR REAR EXIT VERTICAL TERMINATION

Simple venting configurations.

See graph to determine the required vertical rise V

T

for the

required horizontal run H

T

.

REQUIRED

VERTICAL RISE

IN FEET

(METERS)V

T

HORIZONTAL VENT RUN PLUS OFFSET IN FEET

(METERS) H

T

The shaded area within the lines represents acceptable

values for H

T

and H

T

0

5

(1.5)

10

(3.1)

15

(4.6)

20

(6.1)

40 (12.2)

10 (3.1)

20 (6.1)

30 (9.1)

3 (0.9)

(H

T

) < (V

T

)

18.2A

For vent configurations requiring one or more 90° elbows (top exit) or one or more 90° elbows

(rear exit), the following formulas apply:

Formula 1: H

T

< V

T

Formula 2: H

T

+ V

T

< 40 feet (12.2m)

Example:
V

1

= 5 FT (1.5m)

V

2

= 6 FT (1.8m)

V

3

= 10 FT (3.1m)

V

T

= V

1

+ V

2

+ V

3

= 5FT (1.5m) + 6FT (1.8m) + 10FT (3.1m) = 21 FT (6.4m)

H

1

= 8 FT (2.4m)

H

2

= 2.5 FT (0.8m)

H

R

= H

1

+ H

2

= 8FT (2.4m) + 2.5FT (0.8m) = 10.5FT (3.2m)

H

O

= .03 (four 90° elbows - 90°)

= .03 (360° - 90°) = 8.1 FT (2.5m)
H

T

= H

R

+ H

O

= 10.5FT (3.2m) + 8.1FT (2.5m) = 18.6FT (5.7m)

H

T

+ V

T

= 18.6FT (5.7m) + 21FT (6.4m) = 39.6FT (12.1m)

Formula 1:

H

T

< 3.5V

T

18.6 FT (5.7m) < 21 FT (6.4m)

Formula 2:

H

T

+ V

T

< 40 FT (12.2m)

39.6FT (12.1m) < 40 FT (12.2m)

Since both formulas are met, this vent configuration is acceptable.