Warning – Napoleon Fireplaces Grandville 36 - BGD36 Manuel d'utilisation

Page 25

Advertising
background image

25

W415-0773 / F / 08.26.13

EN

5.4.1 GD36 HORIZONTAL INSTALLATION

5.1 WALL AND CEILING PROTECTION

For clearances to combustible materials from the vent pipe, see “FRAMING” section.

!

WARNING

DO NOT FILL THE SPACE BETWEEN THE VENT PIPE AND ENCLOSURE WITH ANY TYPE OF

MATERIAL. DO NOT PACK INSULATION OR COMBUSTIBLES BETWEEN CEILING FIRESTOPS.

ALWAYS MAINTAIN SPECIFIED CLEARANCES AROUND VENTING AND FIRESTOP SYSTEMS.

INSTALL WALL SHIELDS AND FIRESTOPS AS SPECIFIED. FAILURE TO KEEP INSULATION OR

OTHER MATERIALS AWAY FROM VENT PIPE MAY CAUSE FIRE.

A.

Assemble the two halves of the vent sleeve by aligning the holes that

come together to make a rectangular shape (lip to the outside). Secure
using 6 of the screws supplied in the manual baggie.

NOTE: Screws not required in two blind holes.

B.

Fit the fi restop spacer into one end of the vent sleeve and secure

through the aligned holes on the top, bottom, and sides with the
remaining 5 screws supplied.

This application occurs when venting through an exterior wall.
Having determined the air terminal location, cut and frame
a hole in the exterior wall 9 7/8” (250.8mm) wide by 11
3/8” (288.9mm) high to accommodate the fi restop sleeve
assembly.


The length of the vent shield may be cut shorter for
combustible walls that are less than 8 1/2” (215.9mm)
thick but the vent shield must extend

the full depth of the combustible wall.

C.

Insert the fi restop sleeve assembly into the wall,

mark the wall depth and trim the vent sleeve to
suit. The screws that secure the vent sleeve may
need to be repositioned to ensure a rigid assembly is
maintained.

D.

Apply a bead of caulking (not supplied) to the inside

surface of the fi restop fl ange and secure the assembly
to the wall. (Ensure that the rectangular shaped
assembly is installed to maintain 2” (50.8mm) from the
top of the vent).

E.

Once the vent pipe is installed in it’s fi nal position, apply

high temperature sealant W573-0002 (not supplied)
between the pipe and the fi restop.

20.1B

2” (50.8mm)

1” (25.4mm)

TOP

FIRESTOP
SPACER

VENT
SLEEVE

VENT
SHIELD

BLIND
HOLES

11

3/8

” (288.9mm)

DETERMINE

THE CORRECT

HEIGHT

FIRESTOP

SLEEVE

ASSEMBLY

FLANGE

CAULKING

1” (25.4mm)

9

7/8

” (250.8mm)

!

WARNING

THE FIRESTOP ASSEMBLY MUST BE INSTALLED WITH THE VENT SHIELD TO THE TOP.

TERMINALS MUST NOT BE RECESSED INTO A WALL OR SIDING MORE THAN THE DEPTH OF THE

RETURN FLANGE OF THE MOUNTING PLATE.

DRAFT