Safety instructions, Charge controller related – Samlex America SCC-30AB Manuel d'utilisation

Page 4

Advertising
background image

4

1

SAFETY INSTRUCTIONS

batteries can produce a short circuit current high enough to weld a ring or the like to metal

and cause a severe burn.

• If you need to remove a battery, always remove the ground terminal from the battery first.

Make sure that all the accessories are off so that you do not cause a spark.

Charge Controller related

• Please ensure the inputVoltage fed to the Charge Controller does not exceed 50 VDC to

prevent permanent damage to the Charge Controller. Ensure that the maximum Open Circuit

Voltage Voc of the 12V nominal Solar Panel / Solar Array is less than 50V. If two 12V nominal

Solar Panels are being used in series to make a 24 V nominal Solar Array, make sure that the

maximum Open Circuit Voltage Voc of each of the 12 V Panels is less than 25V.

• Do not exceed the maximum current rating of 30 A. The Short Circuit Current of the Solar

Array should be less than 30A.

• Do not exceed a Battery Voltage of 24V (nominal) . Do not use a battery less than 12V.

• Charge only 12 or 24V Lead-Acid batteries when using the standard battery charging

programs or Ni-Cd batteries when DIP Switch number 2~4 is in the ON position.

• DO NOT short circuit the PV array or load while connected to the controller. This will damage

the controller.

• The controller should be protected from direct sunlight. Ensure adequate space for air flow

around the controller’s face plate.

• Do not install in a sealed compartment with batteries.

• Never allow the solar array to be connected to the controller with the battery disconnected.

This can be a dangerous condition with high open-circuit solarVoltage present at the

terminals.

• Use only copper wire with minimum 75°C insulation rating, and between 10 AWG (5.2 mm

2

)

and 14 AWG (2.1 mm

2

) gauge.

• The Negative system conductor should be properly grounded. Grounding should comply with

local codes.

Advertising