GENERAL INFORMATION: BATTERIEs

PERCENTAGE OF

FULL CHARGE

STANDING VOLTAGE OF

12V NOMINAL BATTERy

Cell Voltage (12V BATTERy

HAS 6 CELLS IN SERIES)

100%

12.63V

2.105V

90%

12.6V

2.10V

80%

12.5V

2.08V

70%

12.3V

2.05V

60%

12.2V

2.03V

50%

12.1V

2.02V

40%

12.0V

2.00V

30%

11.8V

1.97V

20%

11.7V

1.95V

10%

11.6V

1.93V

0%

= / < 11.6V

= / < 1.93V

Table 3.3. State of Charge versus Standing Voltage – 12V Battery

Check the individual cell Voltages. If the inter cell Voltage difference is more than a
0.2V, the battery will have to be equalized. Please note that only the non-sealed /
vented / flooded / wet cell batteries are equalized. Do not equalize sealed / VRLA type
of AGM or Gel Cell Batteries (unless allowed by the manufacturer).

Battery Efficiency

A lead-acid battery has an efficiency of only 75% - 85%. The energy lost appears as
heat and warms the battery. This means that the Ampere Hour (Ah) energy required
to charge a battery to its full rated capacity will be approximately 120% to 130%
higher than the Ah capacity rating of the battery.

Depth of Discharge and Battery Life

The more deeply a battery is discharged on each cycle, the shorter the battery life.
Using more batteries than the minimum required will result in longer life for the
battery bank. A typical life cycle chart is given in the Table below:

T

able 3.4. Typical Cycle Life Chart

DEPTH OF DISCHARGE

% OF Ah CAPACITy

CyCLE LIFE OF

GROUP 27 / 31

CyCLE LIFE OF

GROUP 8D

CyCLE LIFE OF

GROUP GC2

10

1000

1500

3800

50

320

480

1100

80

200

300

675

100

150

225

550

It is recommended that the depth of discharge should be limited to 50%.