Parts list for humidifier – GeneralAire 1099LHS Legacy Manuel d'utilisation

Page 3

Advertising
background image

950-14 DRAIN PAN

FORM NO. 1099-56 REV. E

Turn on water supply and check operation of humidifier. Set humidistat to
a demand setting. With the furnace off, the solenoid valve should be
closed. Start the furnace, the solenoid valve should open when the
blower or burner circuit is energized. Check flow of water through
distributor trough and evaporator pad. The standard GA4299 (ORANGE)
orifice will supply approximately 4.75 GPH of water at a line water
pressure of 60 psi. For low water pressures (20-40 psi) a larger (BLUE)
orifice GA4232 is available to provide the same flow. Leave humidistat
set at the recommended setting.

Connect drain hose to 1/2" spout on humidifier cabinet using hose clamp if
necessary. Run 1/2" hose to suitable drain such as floor drain, sewer or laundry
sink. Be sure hose has continuous slope and is not kinked at any point.

8

9

Litho in U.S.A.

PARTS LIST FOR HUMIDIFIER

FILL OUT AND MAIL THIS

WARRANTY CARD AND

LITERATURE REQUEST FORM

A

IR

C

LEANERS AND

A

IR

P

URIFIERS

H

UMIDIFIERS

D

IGITAL

H

UMIDITY

G

AGE

A

IR

F

ILTER

G

AGE

F

UEL

O

IL

F

ILTERS AND

A

CCESSORIES

900-11 DAMPER KNOB
950-5 DAMPER DISC
950-2 SIDE PANEL
DISCHARGE

900-40 PAD RAIL

GA23 EVAPORATOR PAD

950-15 DISTRIBUTOR TROUGH

950-13 COVER

GA4299 ORIFICE

P102 COMPRESSION SLEEVE

P101 COMPRESSION NUT

950-1 CHASSIS
900-9 NOZZLE
900-10 SPOUT
GA4235 DISTRIBUTION
TUBE

GA4040 SOLENOID VALVE ASM.

GA4004 STAINER SCREEN

P102 COMPRESSION SLEEVE

P101 COMPRESSION NUT

R

P189 BRASS TUBE INSERT

747-38 TUBING KIT
(AVAILABLE)

Fresh Indoor Air Quality

3