570 SERIES

DOWN FLOW

RETURN AIR

WARM AIR

WARM AIR

DRAIN

3

3

Connect by-pass pipe to collar and humidifier cabinet. Using
holes at top and bottom of side panel discharge, pierce 2
self tapping screws through by-pass pipe.

1

PRECAUTION: The installer should be an experienced service technician. Disconnect electrical power before
beginning installation. Do not install where temperatures fall below 32 degrees F or where plenum temperatures
exceed 150 degrees F. When wiring into a multi-speed blower circuit see Step 6.

FOR INSTALLATION ON A VERTICAL

PLENUM SURFACE OF ANY

FORCED AIR FURNACE

INSTALLER: PLEASE FILL OUT AND MAIL WARRANTY CARD AFTER INSTALLATION IS
COMPLETE. LEAVE INSTALLATION INSTRUCTIONS WITH HOME OWNER

INSTALLATION: The humidifier may be mounted with the 6" outlet to
the right or left by inverting the cabinet and reversing the positions of
the distributor trough and drain pan. The humidifier may be mounted
on the warm or return air plenum with equal efficiency.
See Typical Installations.

ADDITIONAL MATERIALS THAT MAY BE NECESSARY:
1. 1/4" diameter plastic supply tubing or 1/4" copper
supply tubing for hot water applications
2. 6" diameter galvanized by-pass pipe
3. electrical wire and wire nuts
4. current sensing relay (G.F. Model #GA50 suggested)
5. #8 self piercing sheet metal screws

FLOW-THROUGH

BYPASS HUMIDIFIER

COPPER
TUBING

PLASTIC
TUBING

Mount the self tapping saddle valve or code valve on either a cold
or a hot water pipe. A side or top mount is best to avoid clogging
from pipe sediment. Connect 1/4” O.D. tubing to the saddle valve.
Copper tubing requires a brass compression nut and brass sleeve.
Plastic tubing requires a brass insert inside the tubing, a plastic
sleeve on the outside with a brass compression nut.
NOTE: DO NOT USE PLASTIC TUBING ON HOT WATER OR IN
CONTACT WITH ANY HOT PLENUM SURFACE OR DUCT.
INSTALLATION OF THIS SADDLE VALVE MUST MEET OR
EXCEED LOCAL CODES AND ORDINANCES.

4

2

1

2

GENERALAire

AC SERIES

HIGH EFFICIENCY AIR CLEANER

UP FLOW

RETURN AIR

WARM AIR

DRAIN

R

R

Fresh Indoor Air Quality

FORM NO. 570-18 REV. F

6”

9-1/2”

8-7/8”

The GeneralAire model 570 may be installed on either the
supply or return plenum of a forced air handling system. Select
a location for the humidifier that allows for service and
maintenance. Cut out a rectangle 8-7/8” wide by 9-1/2“ tall.
Extend horizontal centerline of cut out to the adjacent plenum.
Cut a 6” hole 10” to 15” from side of humidifier, on cabinet
centerline, using connecting collar as guide. The bypass is
reversible and can be mounted on the right or left side of the
humidifier.

Humidifier is self retaining. Slide top side in first, then slide
chassis down. Level chassis and install center screws. If
by-pass pipe installs to opposite side of chassis, bend clip on
chassis, remove side discharge, and reinstall discharge to
opposite side of chassis. Install remaining four corner screws.