AD PANEL – USE ONLY WITH GE TED, THED, SE AND FB CIRCUIT BREAKER. #2/0 AWG MAXIMUM
WIRE.
PANNEAU AD – N’UTILISER QUE LES DISJONCTEURS GE DU TYPE TED, THED, SE, FBSECTION DES
MAXIMALE DES FILS 2/0 AWG
USE AF FRONTS WITH AB BOXES / POUR LES BOITIERS AB, UTILISER LES PLAQUES AVANT AF
MAIN
/
DISJ. PRINCIPAL BRANCH
/
DÉRIVATIONS
I.C RATING
TYPE
MAX. AMP
TYPE
POLES
AMP. RANGE
FCL
100 FBV 2,3 15-100
TED
FCH
100 TED
1,2,3 15-100
SEP
150
TED
1, 2, 3
15–100
200,000
THED
3 150
AMPERES
FBV
2,3
15-100
@ 240 VAC
100
SED, SEH, SEL
2,3
15-150
MAX
R FUSE
200
SEH, SEL
2, 3
15–150
SFH, SFL
2, 3
70–250
FBV
2,3
15-100
J OR T
SEH, SEL
2, 3
15–150
FUSE
400
SFH, SFL
2, 3
70-250
600
SEH,
SEL
2,3
15-150
SFP
250
TED
1, 2, 3
15–100
FBV
2,3
15-100
SEL, SEH
2,3
15-150
TED,
THED
2,3
150
SGP
400
SEH, SEL
2, 3
15–150
TFJ
2,
3
70–225
SFH,
SFL
2,3
70-250
FBV
2,3
15-100
FCN 100 TED
1,2, 3
15-100
SEL
150
TED
1, 2, 3
15–100
100,000
THED
3 150
AMPERES
FBV
2,3
15-100
@ 240 VAC
SFL
250
TED, THED, FBV
2, 3
15–100
MAX
225
TED, THED
2, 3
150
FCV 100 TED
1,2, 3
15-100
85,000
SEL
150
TED
1, 2, 3
15–100
AMPERES
THED
3 150
@ 240 VAC
FBV
2, 3
15-100
MAX
TED
2,
3
15–150
SGL
400
FBV
2,3
15-100
TFJ
2,
3
70–225
FBV 2,3 15-100
FCV 100
TED 1,2,3 15-100
SEH
150
TED
1, 2, 3
15–100
3
110–150
65,000
FBV
2,3
15-100
AMPERES
SFH
250
TED
1, 2, 3
15–100
@ 240 VAC
2, 3
110–150
FBV
2,3
15-100
MAX THED
150
TED
2,
3
110–150
SGH
600
TED
1
15-30
3
110-150
TFJ
2,
3
70–225
FCS, SEH
150
TED
1, 2, 3
15–100
THED
150
TED
2,
3
15–150
42,000
TED
1
15–30
AMPERES 225
TED
3
110–150
@ 240 VAC
SGD
TFJ
2, 3
70–225
MAX SGH
TED
1 15–30
600
3
110–150
TFJ
2,
3
70–225
TJJ
600
TED
2,
3
15–150
TFJ
2,
3
70–225
22,000 TFJ,
TJJ
225 TED
2,
3 110–150
AMPERES SFH 250
@ 240 VAC
TJJ, SGH
600
TED
3
110–150
MAX SFH
250
TED
2,
3
110–150
150,000 FCL
100
TED
1 15-50
AMPERES
THED
1 15-30
@ 277 VAC MAX
FCN
100
THED
1
15-30