Wiring Diagram / Schéma unifiliare
3 Phase – 225A Max
1 Phase – 225A Max.
USE COPPER OR ALUMINUM WIRE
USE 60º C OR 75ºC AMPACITY SIZED WIRE ON LINE AND NEUTRAL AND EQUIPMENT GROUND
TERMINALS, EXCEPT AS NOTED BELOW
•
REFER TO CIRCUIT BREAKERS FOR ALLOWABLE WIRE TEMPERATURE RATING, WIRE SIZE
AND TIGHTENING TORQUE, EXCEPT AS NOTED BELOW.
o
USE #1 AWG. MAXIMUM, 75ºC WIRE FOR 90A AND 100A HORIZONTAL
MOUNTED Q-LINE BREAKERS ONLY.
o
USE #3 AWG. MAXIMUM 75ºC, COPPER ONLY WIRE FOR 90-100A Q-LINE
BREAKER & TEY MAIN BREAKERS HORIZONTALLY MOUNTED IN A 7 5/8” WIDE
BOX
o
USE #3 AWG, MAXIMUM 60ºC, COPPER ONLY WIRE FOR TEY 80A, MAX.
HORIZONTALLY MOUNTED BRANCH BREAKERS.
LE CUIVRE D'USAGE OU LE FIL D'ALUMINIUM
L'USAGE 60º C OU 75º AMPACITY DE C A CALIBRE LE FIL CONNECTEE ET NEUTRE ET TERMINAUX DE
SOL D'EQUIPEMENT, SAUF COMME REPUTE AU DESSOUS
•
Se REFERER AUX DISJONCTEURS POUR LE CLASSEMENT DE TEMPERATURE DE FIL
ADMISSIBLE, A LA TAILLE DE FIL ET A RESSERRER LE MOMENT DE TORSION, SAUF COMME
REPUTE AU DESSOUS
o
L'USAGE #1 AWG. LE MAXIMUM, 75ºle FIL DE C POUR L'HORIZONTALE DE 90A ET
100A A MONTE LES CONCASSEURS DE Q-LIGNE SEULEMENT.
o
L'USAGE #3 AWG. LE MAXIMUM 75ºle C, LE CUIVRE SEULEMENT FIL POUR 90-100A
CONCASSEUR DE Q-LIGNE & TEY LES CONCASSEURS PRINCIPAUX ONT MONTE
HORIZONTALEMENT DANS UN 7 5/8” LA BOITE LARGE
o
L'USAGE #3 AWG, LE MAXIMUM 60ºle C, LE CUIVRE SEULEMENT FIL POUR TEY 80A,
LE MAXIMUM. LES CONCASSEURS HORIZONTALEMENT DE BRANCHE MONTES.