Wiring diagram / schéma unifiliare – GE Industrial Solutions A-Series II Lighting Panels Manuel d'utilisation

Page 14

Advertising
background image

14


Wiring Diagram / Schéma unifiliare

3 Phase – 225A Max

1 Phase – 225A Max.

USE COPPER OR ALUMINUM WIRE

USE 60º C OR 75ºC AMPACITY SIZED WIRE ON LINE AND NEUTRAL AND EQUIPMENT GROUND

TERMINALS, EXCEPT AS NOTED BELOW

REFER TO CIRCUIT BREAKERS FOR ALLOWABLE WIRE TEMPERATURE RATING, WIRE SIZE
AND TIGHTENING TORQUE, EXCEPT AS NOTED BELOW.

o

USE #1 AWG. MAXIMUM, 75ºC WIRE FOR 90A AND 100A HORIZONTAL
MOUNTED Q-LINE BREAKERS ONLY.

o

USE #3 AWG. MAXIMUM 75ºC, COPPER ONLY WIRE FOR 90-100A Q-LINE
BREAKER & TEY MAIN BREAKERS HORIZONTALLY MOUNTED IN A 7 5/8” WIDE
BOX

o

USE #3 AWG, MAXIMUM 60ºC, COPPER ONLY WIRE FOR TEY 80A, MAX.

HORIZONTALLY MOUNTED BRANCH BREAKERS.

LE CUIVRE D'USAGE OU LE FIL D'ALUMINIUM

L'USAGE 60º C OU 75º AMPACITY DE C A CALIBRE LE FIL CONNECTEE ET NEUTRE ET TERMINAUX DE

SOL D'EQUIPEMENT, SAUF COMME REPUTE AU DESSOUS

Se REFERER AUX DISJONCTEURS POUR LE CLASSEMENT DE TEMPERATURE DE FIL
ADMISSIBLE, A LA TAILLE DE FIL ET A RESSERRER LE MOMENT DE TORSION, SAUF COMME
REPUTE AU DESSOUS

o

L'USAGE #1 AWG. LE MAXIMUM, 75ºle FIL DE C POUR L'HORIZONTALE DE 90A ET
100A A MONTE LES CONCASSEURS DE Q-LIGNE SEULEMENT.

o

L'USAGE #3 AWG. LE MAXIMUM 75ºle C, LE CUIVRE SEULEMENT FIL POUR 90-100A
CONCASSEUR DE Q-LIGNE & TEY LES CONCASSEURS PRINCIPAUX ONT MONTE
HORIZONTALEMENT DANS UN 7 5/8” LA BOITE LARGE

o

L'USAGE #3 AWG, LE MAXIMUM 60ºle C, LE CUIVRE SEULEMENT FIL POUR TEY 80A,
LE MAXIMUM. LES CONCASSEURS HORIZONTALEMENT DE BRANCHE MONTES.