Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08

45

INTERIOR

Heat Shield or

Extended

Heat Shield

Wall Shield

Firestop

Heat Shield

1-1/2 in. (38 mm) min.

overlap

SHEATHING

Slip Section

can be extended

Inner Vent

Outer Vent

EXTERIOR

Figure 10.20 Venting through the wall

Note: When using termination caps with factory-supplied
heat shield attached, no additional wall shield ¿ restop is
required on the exterior side of a combustible wall.

J. Install Horizontal Termination Cap

WARNING! Risk of Fire! The telescoping À ue section
of the termination cap MUST be used when connecting
vent.

• 1-1/2 (38 mm) minimum overlap of À ue telescoping

section is required.

Failure to maintain overlap may cause overheating and
¿ re.

Vent termination must not be recessed in the wall. Siding
may be brought to the edge of the cap base.

• Flash and seal as appropriate for siding material at

outside edges of cap.

• When installing a horizontal termination cap, follow

the cap location guidelines as prescribed by current
ANSI Z223.1 and CAN/CGA-B149 installation codes
and refer to Section 6 of this manual.

CAUTION! Risk of Burns! Local codes may require
installation of a cap shield to prevent anything or anyone
from touching the hot cap.

NOTICE: For certain exposures which require superior
resistance to wind-driven rain penetration, a À ashing kit and
HPC caps are available. When penetrating a brick wall, a
brick extension kit is available for framing the brick.