C. Install the Ceiling Firestop

A ceiling ¿ restop MUST be used between À oors and at-
tics.

• Frame an opening 10 in. by 10 in. (254 mm by 254

mm) whenever the vent penetrates a ceiling/À oor (see
Figure 8.3).

• Frame the area with the same sized lumber as used in

ceiling/À oor joist.

• The ceiling ¿ restop may be installed above or below

the ceiling joists when installed with a attic insulation
shield. It must be under joists between À oors that are
not insulated. Refer to Figure 8.4.

• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insulation around
the vent. Insulation must be kept back from the pipe to pre-
vent overheating.

Figure 8.3

Installing Ceiling Firestop

Figure 8.4 Installing the Attic Shield

Attic Above

10 in. (254 mm)

Hole should measure

10 in. x 10 in.

(254 mm x 254 mm)

inside to inside

10 in.

(254 mm)

3 fasteners

per side

Ceiling firestop

installed below ceiling.

Ceiling firestop

installed above ceiling.

Install attic insula-
tion shields before
or after installation
of vent system.