E. vent diagrams, Top vent - horizontal termination – Quadra-Fire QFP44 Manuel d'utilisation

Page 30

Advertising
background image

Quadra-Fire • QFP44 • 4051-300 Rev M • 09/08

30

H

1

V

1

To replace the ¿ rst starter elbow with two 45° elbows,
refer to Figure 7.4. All other 90° elbows can be replaced
with two 45° elbows.

General Rules:

SUBTRACT 3 ft. from the total H measurement for each
90° elbow installed horizontally.

• SUBTRACT 1-1/2 ft. from the total H measurement for

each 45° elbow installed horizontally.

• A maximum of three 90° elbows (or six 45° elbows)

may be used in any vent con¿ guration. Some elbows
may be installed horizontally. See Figure 7.9.

• Elbows may be placed back to back anywhere in the

system as long as the ¿ rst 90° elbow is a starter elbow
except as shown in Figure 7.4.

• When penetrating a combustible wall, a wall shield

¿ restop must be installed.

• When penetrating a combustible ceiling, a ceiling

¿ restop must be installed.

• Horizontal runs of vent do not require vertical rise;

horizontal runs may be level.

E. Vent Diagrams

Figure 7.3

One Elbow

1. Top Vent - Horizontal Termination

V

1

Min.

V

1

Max.

H

1

Max.

3 ft (.91 m)

-

1.5 ft (.46 m)

4 ft (1.22 m)

-

6 ft (1.83 m)

5 ft (1.52)

-

11 ft (3.35 m)

6 ft (1.83 m)

-

13 ft (3.96 m)

7 ft (2.13 m)

-

15 ft (4.57 m)

10 ft (3.05 m)

25 ft (7.62 m)

20 ft (6.10 m)