4.1.2 SECTIONS

Add chimney sections, according to the manufacturers installation instructions. The chimney must extend at
least, 3 feet (0.9m) above its point of contact with the roof and at least 2 feet (0.6m) higher than any wall, roof,
building or obstacle within 10 feet (3.1m) horizontally.

59.1B

3 FT

(0.9m)

MIN

3 FT

(0.9m)

MIN

10 FT

(3.1m) OR

MORE

FLAT ROOF

WALL

10 FT (3.1m)

TO NEAREST

ROOFLINE

RIDGE

LESS THAN

10 FEET

(3.1m)

2 FT (0.6m) MIN

3 FT

(0.9m)

MIN

2 FT (0.6m)

MIN

LESS THAN

10 FEET

(3.1m)

3 FT

(0.9m)

MIN

2 FT (0.6m)

MIN