3 minimum clearance to combustibles, 4 minimum enclosure clearances – Napoleon Fireplaces High Country 6000 - NZ6000 Manuel d'utilisation

Page 23

Advertising
background image

W415-0594 / E / 10.19.12

23

5.3 MINIMUM CLEARANCE TO COMBUSTIBLES

Framed Enclosure
Rear

- 0" to stand-offs (rear)

Sides

- 6" to sides*

Ceiling

-

120" from the base of the appliance (unless shielded with metal

(enclosure)

studs and cement board)

Ceiling

- 84" from the base of the appliance

(in front of appliance)
Chimney

- 2" (follow manufacturers instructions)

Hot air Gravity Ductwork Insulation

- 1"

Solid Pack Chimney
Ceiling

- 120" from the base of the appliance (unless shielded with metal

(enclosure)

studs and cement board).

Air Cooled
Ceiling

- 84" from the base of the appliance

(enclosure)

87"

61

1

/

2

"

123"

50"

30

3

/

4

"

50"

15” required

if coiling

liner

1/2" Cement board

finishing

A

Shown with air intake liner coiled to create a cold trap.
OR
A minimum of 6" is required to combustibles from the
side of the unit. This is only if the intake liner is routed
below the 2" projection of the outer casing of the unit.
If the intake liner is routed vertically along the side of
the unit then a spacing of 7" is required.

When framing in unit, allow for fi nishing material
thickness.

A minimum of 6" is required to combustibles from the
side of the unit. This is practical only if the intake liner
is routed below the 2" projection of the outer casing of
the unit. If the intake liner is routed vertically along the
side of the unit then a spacing of 7" is required.

2 layers of 1/2" cement

board needed to fi ll gap A.

30

3

/

4

"

61

1

/

2

"

50"

21"

MIN

6"

MIN

5.4 MINIMUM ENCLOSURE CLEARANCES