PETROLEUM GASES, ANSI/NFPA 58 AND CSA B149.1, NATURAL GAS AND PROPANE
INSTALLATION CODE.

PIPING: THIS HEATER MUST BE INSTALLED BY A QUALIFIED GAS TECHNICIAN
FOLLOWING LOCAL CODES PUBLISHED BY THE AUTHORITY HAVING JURISDICTION.
SIZING OF SUPPLY PIPING MUST BE DETERMINED USING THE LENGTH OF PIPE RUN AS
WELL AS TOTAL BTUH RATING OF THE APPLIANCE(S). APPROPRIATE PIPING TABLES
MUST BE USED TO DETERMINE SIZE OF SUPPLY PIPING DEPENDANT ON THE LENGTH
OF RUN FROM SOURCE.

PRESSURES

THIS HEATER MUST BE SUPPLIED BY PRESSURES INDICATED ON THE APPROVAL LABEL.
OVER PRESSURE MAY CAUSE CONTROLS TO FAIL. DO NOT SUPPLY THIS UNIT WITH
MORE THAN ½ PSIG (14.0 IN. W.C.)

NOTE: A SECOND STAGE REGULATOR MUST BE INSTALLED IF THE SUPPLY PRESSURE
EXCEEDS ½ PSIG.


FUEL

THIS HEATER WILL OPERATE ON PROPANE OR NATURAL GAS—NOT BOTH. THE
MANIFOLD PRESSURES ARE LISTED ON THE APPROVAL LABEL. TO DETERMINE WHICH
FUEL TO USE SEE RATING PLATE. DO NOT ATTEMPT TO USE THE HEATER WITHOUT
CONSULTING THE RATING PLATE.

NOTE: THE PROPER MAIN BURNER ORIFICE MUST BE INSTALLED AND RATING PLATE
MUST REFLECT THE FUEL THE HEATER IS BURNING. DO NOT OPERATE THE HEATER
WITHOUT CONSULTING THE RATING PLATE.

HEATER CONVERSION MUST BE DONE BY A QUALIFIED TECHNICIAN AND RATING PLATE
MUST REFLECT ANY CHANGE.

APPROXIMATE RUN TIMES WITHOUT USING RECIRCULATING DUCTS-
NATURAL GAS OPERATION

INPUT BTU’s cfh

315,000 315
340,000 340
399,000 399

APPROXIMATE RUN TIMES WITHOUT USING RECIRCULATING DUCTS-
PROPANE OPERATION

INPUT BTU’s Lbs per hour

315,000 14.65

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)

6 Carson Court, Brampton, ON, CANADA, L6T 4P8

Tel: (905) 793-2525 | Fax: (905) 793-8768 |

www.campoequipment.com