DISCHARGE DUCTS 20” on outlet with optional (4) X 12” outlet

THIS HEATER IS FOR USE WITH AND WITHOUT DUCTWORK
WHEN USING DUCTWORK AVOID ANY KINKS OR SHARP BENDS.
INSUFFICIENT INLET AIR OR INSUFFICIENT DISCHARGE AIR WILL CAUSE
THE HEATER TO OVERHEAT.

BLAZE 700 D/G MAINTENANCE INSTRUCTIONS

WARNING

EVERY CONSTRUCTION HEATER SHOULD BE INSPECTED

BEFORE EACH USE, AND AT LEAST ANNUALLY BY A QUALIFIED SERVICE
PERSON. INCORRECT MAINTENANCE MAY RESULT IN IMPROPER
OPERATION OF THE HEATER AND SERIOUS INJURY COULD OCCUR.

HOSE ASSEMBLIES
The hose assemblies shall be visually inspected prior to each use of the heater. If it is evident there is excessive
abrasion or wear, or the hose is cut, it must be replaced prior to the heater being put into operation. The replacement
hose assembly shall be that specified by the manufacturer.

TEMPERATURE CONTROLLER AND THERMOCOUPLE

The temperature controller protocols should be checked every heating season to ensure the burner will shutdown if
temperature exceeds 250 F (US)/290 F (CA) at the outlet duct. This can be accomplished by restricting the air flow
through the unit. After tests are complete, remove restrictors as both inlet and outlet ducts must be open for proper
operation.

The temperature controller setting of 95F has been selected to allow for preheating of the heat exchanger to ensure
that only heated air is allowed to enter the space. Upon satisfying the need for heat, the temperature controller will
continue to run the supply fan until the heat exchanger has cooled sufficiently. This feature will help prolong the life of
the heat exchanger. The temperature controller must be replaced if the fan motor does not shut off after the heat
exchanger has cooled down.

Temperature Controller Protocols

Fan Turns on at 95 F

Out # 2 is set at 190º (This will cycle the burner off 190º and back on at 160º.) If the burner reset light goes on; you
need to go into the burner compartment in the door under the air supply. For the Beckett CG10A the Honeywell
controller must be reset by pressing the reset button. For the Beckett CF800 oil burner the Beckett Genisys controller
located on the control panel must be pressed.

Out # 3 is set at 260º (This will cause burner to go out on high temp.)
If this occurs you will have to reset the temperature controller, by holding down the “OVER HEAT RESET” push
button.

During cool down the unit cools to 80F and then shuts down.



ELECTRICAL