STARTING HEATER

1.)

ENSURE HEATER IS ON FLAT, LEVEL GROUND BEFORE STARTING, CANOPY AND FAN GUARDS
MUST BE CLOSED.

2.)

MAKE SURE “MAIN SWITCH” IS IN “OFF” POSITION.

3.)

WIRE IN SUPPLY CORD TO 208V-240V SUPPLY WITH GROUND.

Power Supply Installation
Single phase operation use L1 (RED) and L2 (BLACK) plus green for ground.
Three phase operation use L1 (RED), L2 (BLACK) and L3 (WHITE) plus green for ground.
4.) SELECT “GAS” OR “OIL”.
5.)

TURN “MAIN SWITCH” TO “ON” POSITION.

6.)

TURN “CONTROLS” SWITCH TO “ON” POSITION.

7.)

FOR THERMOSTAT OPERATION FLIP SELECTOR SWITCH TO “STAT ON” POSITION. IF YOU ARE NOT

USING A THERMOSTAT FLIP SELECTOR SWITCH TO “BYPASS” POSITION.

8.)

TURN “HEAT/FAN” SWITCH TO “HEAT POSITION”.

Please Note: When using a generator for electrical supply, make sure the generator is properly grounded and
is running at a 60HZ frequency. In the event that a generator is being used and the generator runs out of fuel,
make sure the heater “MAIN SWITCH” is in the “OFF” position before restarting generator, failure to do so
may damage heater.


STOPPING HEATER

1.) Close main gas supply valve while heater is operating or if operating heater with oil skip to # 2.)
2.) Flip “HEAT/FAN” selector switch to “OFF” position. The supply fan will continue to operate until the heat

exchanger has sufficiently cooled. Do not disconnect main power until supply fan has stopped running and
“MAIN SWITCH” is on “OFF” position.

3.) Disconnect heater from gas supply OR disconnect fuel oil lines.



WARNING BEFORE REMOVING ANY GUARDS OR SAFETIES TURN “MAIN SWITCH” TO “OFF” POSITION AND
DISCONNECT THE MAIN POWER AS THE SUPPLY FAN WILL CYCLE AUTOMATICALLY.


IF HEATER FAILS TO START

1.) PRESS BURNER RESET BUTTON TO RESET CONTROL ON BECKETT CG10A. FOR OIL OPERATION

PRESS AND HOLD THE RED BUTTON ON THE BECKETT GENISYS CONTROLLER LOCATED ON THE
CONTROL PANEL FOR 3 SECONDS TO RESET.

1.) FOR GAS OPERATION CHECK GAS PRESSURE SUPPLY. SUPPLY AND MANIFOLD PRESSURE MUST

FOLLOW THOSE ON RATING PLATE. FOR OIL OPERATION CHECK FUEL LEVEL, FILTER, NOZZLE
AND SUCTION TUBING.

2.) ENSURE PROPER POWER SUPPLY AND WIRE GAUGE IS BEING USED.
3.) IF HEATER FAILS TO IGNITE AFTER 3 ATTEMPTS, CALL YOUR SUPPLIER FOR SERVICE.

NOTE: IF UNIT HAS BEEN RESET A NUMBER OF TIMES WITHOUT IGNITION -- DO NOT ATTEMPT TO START

THE HEATER: CONTACT A QUALIFIED SERVICE TECHNICIAN.

NOTE: IN OIL OPERATION IF UNIT HAS BEEN RESET A NUMBER OF TIMES WITHOUT IGNITION THERE WILL

BE AN ACCUMULATION OF OIL IN THE COMBUSTION CHAMBER! DO NOT ATTEMPT TO START THE
HEATER: CONTACT A QUALIFIED SERVICE TECHNICIAN.

CAUTION

1.) DO NOT SHUT OFF BY DISCONNECTING SUPPLY CORD. THE HEAT EXCHANGER SHOULD BE

PROPERLY COOLED BEFORE POWER SHUTDOWN.

2.) ALWAYS MAINTAIN ADEQUATE FUEL SUPPLY.