3.) IF GAS BURNER IS INSTALLED HEATER IS FOR USE WITH PROPANE OR NATURAL GAS ONLY. SEE

APPROVAL LABEL.

4.) DO NOT PLUG ANYTHING OTHER THAN THE THERMOSTAT INTO THE “REMOTE STAT” PLUG.
5.) FOLLOW ELECTRICAL REQUIREMENTS SHOWN ON RATING PLATE AND/OR ELECTRICAL

REQUIREMENTS SECTION OF THIS MANUAL.

6.) IN OIL OPERATION DO NOT START THE HEATER WHEN EXCESS OIL HAS ACCUMULATED IN

CHAMBER.

7.) IN OIL OPERATION DO NOT FILL TANK WHILE UNIT IS OPERATING.
8.) IN NO CASE SHOULD POWER CABLES BE SMALLER THAN WHAT IS STIPULATED ON NAMEPLATE

AND INSTRUCTION MANUAL.

9.) IN OIL OPERATION DO NOT USE GASOLINE, CRANKCASE OIL OR HEAVIER THAN NO. 2 FURNACE

OIL.

10.) DO NOT START THE HEATER WHEN THE CHAMBER IS HOT
11.) DO NOT FILL THE TANK WHILE THE UNIT IS OPERATING
12.) DO NOT TAMPER WITH THE UNIT. HAVE A COMPETENT SERVICE-MAN MAKE ANY ADJUSTMENTS
13.) MAX OUTLET TEMPERATURE (U.S./CA) 250F/290F
14.) AT INSTALLATION ELEVATIONS ABOVE 2000 FT (610m), THE APPLIANCE SHALL BE DERATED 4

PERCENT FOR EACH 1000 FT (305m) OF ELEVATION ABOVE SEE LEVEL

15.) SHOULD OVERHEATING OCCUR, OR THE GAS SUPPLY CONTROL SYSTEM FAIL TO SHUT OFF THE

FLOW OF GAS, SHUT OFF THE MANUAL GAS VALVE TO THE UTILITY HEATER BEFORE SHUTTING
OFF THE ELECTRICAL SUPPLY.

16.) DO NOT USE THIS UTILITY HEATER IF ANY PART HAS BEEN UNDER WATER. IMMEDIATELY CALL A

QUALIFIED SERVICE TECHNICIAN TO INSPECT THE HEATER AND REPLACE ANY GAS CONTROL
WHICH HAS BEEN UNDER WATER.

ELECTRICAL REQUIREMENTS: 20 AMPS (1PH) or 10 AMPS (3PH)


INSTALLATION INSTRUCTIONS

1.) The recommendations of local authorities having jurisdiction must be followed. For

recommended installation practices refer to C.S.A. standard B139. (CANADA)

2.) When firing the unit in an enclosed area allow 1 square inch per thousand BTU’s (refer to

C.S.A. B139) to allow the free entry of the air required for operation.

3.) For electrical supply:

208V-240V SUPPLY WITH GROUND.

Power Supply Installation

Single phase operation use L1 (RED) and L2 (BLACK) plus green for ground.

Three phase operation use L1 (RED), L2 (BLACK) and L3 (WHITE) plus green for ground.

4.) Do not operate the unit in partly ventilated areas without a flue pipe or in close proximity to

combustible surfaces or materials.

NOTE: Installation clearances are as follows:

TOP

2 inches

SIDES

6 inches

BURNER END

2 feet

DISCHARGE END

10 feet

VENT CONNECTOR

18 inches

COMBUSTIBLE FLOOR

6 feet

FLUE PIPE CONNECTIONS

CAMPO EQUIPMENT CO. LTD. (ECOBLAZE)

6 Carson Court, Brampton, ON, CANADA, L6T 4P8

Tel: (905) 793-2525 | Fax: (905) 793-8768 |

www.campoequipment.com

P a g e

| 13