VENT TO OUTDOORS

FOR INSTALLATION ON NON-COMBUSTIBLE FLOORS ONLY

When the heater is connected to a flue pipe the flue pipe shall terminate in a vertical section at
least two feet long. Horizontal runs should have rise ratio of 1 in 10 away from the heater. Where
down drafts are liable to occur a vent cap should be used. All venting should correspond with the
CSA B139 standard or local codes
.

CAUTION: HEATER FLUE TEMPERATURES CAN REACH 400F TO 500F THEREFORE IT IS A
RANGE THAT IS BOTH HAZARDOUS TO HUMANS AND HIGHER THAN THE AUTO-IGNITION
TEMPERATURES OF MANY MATERIALS. THEREFORE EXERCISE CAUTION IN HEATER
PLACEMENT AND THE USE OF AN INSULATED GUARD AND STACK IS HIGHLY
RECOMMENDED

.


Horizontal venting runs shall always terminate with a minimum 24” vertical.

NOTE: FOR OPTIMAL COMBUSTION PERFORMANCE A 30” C-VENT FLUE EXTENSION WITH
RAIN CAP IS RECOMMENDED AT ALL TIMES.

Recommended chimney draft - .05 inches of water column

INSTALLATION CLEARANCES

MAXIMUM ALLOWABLE DUCT LENGTHS BLAZE 700 D/G - 200ft
INLET DUCTS 20” on each inlet