Derating Charts for each input

EFT/B immunity

IEC 61000-4-4:
±2 kV at 5 kHz on signal ports

Surge transient immunity

IEC 61000-4-5:
±1 kV line-line(DM) and ±2 kV line-earth(CM) on signal ports

Conducted RF immunity

IEC 61000-4-6:
10V rms with 1 kHz sine-wave 80% AM from 150 kHz...80 MHz

Certifications

Certification (when

product is marked)

(1)

(1)

See the Product Certification link at

http://www.rockwellautomation.com/products/certification

for Declaration of

Conformity, Certificates, and other certification details.

Value

c-UL-us

UL Listed Industrial Control Equipment, certified for US and Canada. See UL File

E65584.

UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for

U.S. and Canada. See UL File E194810.

CE

European Union 2004/108/EC EMC Directive, compliant with:

EN 61326-1; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
EN 61000-6-4; Industrial Emissions
EN 61131-2; Programmable Controllers (Clause 8, Zone A & B)

C-Tick

Australian Radiocommunications Act, compliant with:

AS/NZS CISPR 11; Industrial Emissions

KC

Korean Registration of Broadcasting and Communications Equipment,

compliant with:
Article 58-2 of Radio Waves Act, Clause 3

Environmental Specifications

Attribute

Value

°C

point

32

24

23

60

55

3.9W

4.1W

@Vin=26.4V

26

5.4W

40

28

4.8W

30

5.2W

31

point

°C

32

24
22

55 60

@Vin=30.0V

18

6.8W

3.9W

4.1W

20

5.1W

30

40

19

4.8W

44917

44918