Input Wiring

Basic wiring of input devices to the 1762-IQ32T is shown below.

Basic Input Wiring to the 1762-IQ32T Module

Simplified Input Circuit Diagram

A write-on label is provided with the module. Mark the identification of each terminal with
permanent ink, and slide the label back into the door.

ATTENTION

Sinking/Sourcing Inputs - Sourcing/sinking describes the current flow between
the I/O module and the field device. Sourcing I/O circuits supply (source) current
to sinking field devices. Sinking I/O circuits are driven by a current sourcing field
device. Field devices connected to the negative side (DC Common) of the field
power supply are sinking field devices. Field devices connected to the positive
side (+V) of the field supply are sourcing field devices.