Assemble the wire contacts – Rockwell Automation 1762-IQ32T MicroLogix DC Input Module Manuel d'utilisation

Page 15

Advertising
background image

MicroLogix 1762-IQ32T DC Input Module 15

Publication 1762-IN019B-EN-P - June 2013

Assemble the Wire Contacts

1. Strip the wire insulation to expose 4 mm (5/32 in.) of wire. Crimp pins can accept

22...26 AWG wire.

2. Insert the wire into the crimp pin as far as the wire stop.

3. Crimp the wire barrel around the wire using small needle nose pliers.

4. Crimp the insulation barrel around the wire insulation using small needle nose pliers.

5. Solder wire and wire barrel together using lead-free solder and soldering pencil.

6. Insert the assembled wire contact into the terminal socket. Push the wire contact in until

the tang latches. Make sure the tang is properly latched by lightly pulling on the wire.

ATTENTION

Be careful when stripping wires. Wire fragments that fall into the module could
cause damage. Once wiring is complete, be sure the module is free of all metal
fragments before removing the protective debris strip. Failure to remove the
strip before operating can cause overheating.

4 mm

(5/32 in.)

44916

Wire stop

Wire barrel

Tang

Stripped wire

44921

Insulation barrel

Stripped wire

Tang

44922

Terminal connector

Terminal sockets

Wire contact

Advertising