1747-dps1 network port, 1747-dps2 network port – Rockwell Automation 1747-DPS1, 1747-DPS2 Port Splitter Installation Instructions Manuel d'utilisation

Page 10

Advertising
background image

10 Port Splitters

Publication 1747-IN516B-EN-P - October 2007

1747-DPS1 Network Port

The Network port on the 1747-DPS1 splitter allows message initiation from the
controller as well as ASCII write initiation to be passed through. The port
configuration is fixed at DF1 full-duplex, 19.2 Kbps, 8 bits, no parity, 1 stop bit, and
CRC checksum.

The Network port can source power from the port-splitter’s external Class 2 power
supply to a 1761-NET-AIC or 1761-NET-ENI interface, if a 1761-CBL-AM00 or
1761-CBL-HM02 cable (or equivalent) is used.

1747-DPS2 Network Port

The Network ports on the 1747-DPS2 port splitter allow message initiation from the
controller as well as ASCII write initiation to be passed through.

The Network ports also allow communication with DH-485, DF1 half-duplex, DF1
full-duplex, and DF1 radio modem networks. The communication parameters are
also configurable.

The Network port is programmed as DH485 from the factory.

The Network port is configured with a software utility that you can download from
http://www.ab.com/programmablecontrol/plc/slcsystem/downloads.html.

IMPORTANT

Do not connect a MicroLogix 1100 controller to the Port Splitter Network port.
Permanent damage to the MicroLogix 1100 communication port may result.

IMPORTANT

If a 1761-NET-DNI or 1761-NET-ENI interface is connected to the Network port,
their serial ports must be configured for 19.2 Kbps. Do not attempt to use their
autobaud capability.

IMPORTANT

If a 1761-NET-DNI or 1761-NET-ENI interface is connected to the Network port,
their serial ports must be configured for 19.2 Kbps. Do not attempt to use their
autobaud capability.