Communicate with your armorblock maxum module – Rockwell Automation 1792D-8BIO8E ArmorBlock MaXum 8 Input/8 Output Module Series B Manuel d'utilisation

Page 7

Advertising
background image

ArmorBlock MaXum 8 Input/8 Output Module Series B 7

Publication 1792D-IN033B-EN-P - September 2000

DeviceNet Cable

DeviceNet cables are described in the installation publications for the
cable base of your choice. Refer to the following publications:

1792D-IN009B-EN-P ArmorBlock MaXum Cable Base
Installation Guide

DN-6.7.2 DeviceNet Cable Planning and Installation Manual

Communicate With Your ArmorBlock MaXum Module

This ArmorBlock module’s I/O is exchanged with the master through
a polled, change-of-state, or cyclic connection.

The module consumes and produces input data as follows:

Cyclic - allows configuration of the block as an I/O client. The block
will produce its I/O cyclically at the rate configured.

Polled - a master initiates communication by sending its polled I/O
message to the module. The module consumes the message, updates
outputs, and produces a response. The response has input data and
I/O fault status.

Change-of-State - productions occur when an input changes or a
fault condition occurs. If no input or fault condition change occurs
within the expected packet rate, a heartbeat production occurs. This
heartbeat production tells the scanner module that the module is alive
and ready to communicate.

ATTENTION

!

Power for this unit’s outputs is derived from
DeviceNet power. A short on the output device
could affect DeviceNet operation.

Type of I/O Connections

Consumes

Produces

Cyclic

1 Byte

2 Bytes

Polled

1 Byte

2 Bytes

Change-of-State

1 Byte

2 Bytes